5.4.4 Frequency Converter Address (ADR)
Address format 1–126
•
Bit 7 = 1 (address format 1–126 active).
•
Bit 0–6 = frequency converter address 1–126.
•
Bit 0–6 = 0 broadcast.
The slave returns the address byte unchanged to the
master in the response telegram.
5.4.5 Data Control Byte (BCC)
The checksum is calculated as an XOR-function. Before the
first byte in the telegram is received, the calculated
checksum is 0.
5.4.6 The Data Field
The structure of data blocks depends on the type of
telegram. There are 3 telegram types, and the type applies
for both control telegrams (master
⇒
slave) and response
telegrams (slave
⇒
master).
The 3 types of telegram are:
Process block (PCD)
The PCD is made up of a data block of 4 bytes (2 words)
and contains:
•
Control word and reference value (from master to
slave)
•
Status word and present output frequency (from
slave to master)
ADR
LGE
STX
PCD1
PCD2
BCC
130BA269.10
Illustration 5.5 Process Block
Parameter block
The parameter block is used to transfer parameters
between master and slave. The data block is made up of
12 bytes (6 words) and also contains the process block.
PKE
IND
ADR
LGE
STX
PCD1
PCD2
BCC
130BA271.10
PWE
high
PWE
low
Illustration 5.6 Parameter Block
Text block
The text block is used to read or write texts via the data
block.
PKE
IND
130BA270.10
ADR
LGE
STX
PCD1
PCD2
BCC
Ch1
Ch2
Chn
Illustration 5.7 Text Block
5.4.7 The PKE Field
The PKE field contains 2 subfields:
•
Parameter command and response (AK)
•
Parameter number (PNU)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BB918.10
PKE
IND
PWE
high
PWE
low
AK
PNU
Par
amet
er
commands
and r
eplies
Par
amet
er
number
Illustration 5.8 PKE Field
Bits 12–15 transfer parameter commands from master to
slave and return processed slave responses to the master.
Parameter commands master
⇒
slave
Bit number
Parameter command
15
14
13
12
0
0
0
0
No command.
0
0
0
1
Read parameter value.
0
0
1
0
Write parameter value in RAM (word).
0
0
1
1
Write parameter value in RAM (double
word).
1
1
0
1
Write parameter value in RAM and
EEPROM (double word).
1
1
1
0
Write parameter value in RAM and
EEPROM (word).
1
1
1
1
Read text.
Table 5.5 Parameter Commands
Response slave
⇒
master
Bit number
Response
15
14
13
12
0
0
0
0
No response.
0
0
0
1
Parameter value transferred (word).
0
0
1
0
Parameter value transferred (double
word).
0
1
1
1
Command cannot be performed.
1
1
1
1
Text transferred.
Table 5.6 Response
If the command cannot be performed, the slave sends this
response
0111 Command cannot be performed
and issues
the following fault report in
.
RS485 Installation and Set-...
Design Guide
MG07B102
Danfoss A/S © 03/2016 All rights reserved.
57