L1
L2
L3
PE
Min. 16 mm
2
Equalizing cable
Control cables
All cable entries in
one side of panel
Earthing rail
Cable insula-
tion stripped
Output con-
tactor etc.
Motor cable
Motor, 3 phases and
PLC etc.
Panel
Mains-supply
Min. 200mm
between control
cable, mains cable
and between mains
motor cable
PLC
Protective earth
Reinforced protective earth
130BB965.10
Illustration 6.9 EMC-correct Electrical Installation
For North America use metal conduits instead of shielded cables.
How to Install
VLT Micro Drive Design Guide
MG02K102 - VLT
®
is a registered Danfoss trademark
51
6
6
Содержание VLT Micro Drive PK18