Switching frequency
When frequency converters are used together with Sine-
wave filters to reduce the acoustic noise from a motor, the
switching frequency must be set according to the Sine-
wave filter instruction in
14-01 Switching Frequency
.
Aluminium conductors
Aluminium conductors are not recommended. Terminals
can accept aluminium conductors but the conductor
surface has to be clean and the oxidation must be
removed and sealed by neutral acid free Vaseline grease
before the conductor is connected.
Furthermore, the terminal screw must be retightened after
two days due to the softness of the aluminium. It is crucial
to keep the connection a gas tight joint, otherwise the
aluminium surface will oxidize again.
6.8.4 EMC-Correct Electrical Installation
General points to be observed to ensure EMC-correct
electrical installation.
•
Use only screened/armoured motor cables and
screened/armoured control cables.
•
Connect the screen to earth at both ends.
•
Avoid installation with twisted screen ends
(pigtails), since this ruins the screening effect at
high frequencies. Use the cable clamps provide-
dinstead.
•
It is important to ensure good electrical contact
from the installation plate through the installation
screws to the metal cabinet of the frequency
converter.
•
Use starwashers and galvanically conductive
installation plates.
•
Do not use unscreened/unarmoured motor cables
in the installation cabinets.