Response
The normal response is an echo of the query, returned after the register contents have been passed.
Field Name
Example (HEX)
Slave address
01
Function
06
Starting Address HI
00
Starting Address LO
1D
No. of Points HI
00
No. of Points LO
01
Error Check (CRC)
-
Table 5.1: Normal response frame
5.5.6 Preset Multiple Registers (10
HEX
)
Description
This function presets a value into a sequence of holding registers.
Query
The query message specifies the register references to be preset. Register addresses start at zero, i.e. register 1 is addressed as 0.
Example
Write 65535 (655.35s) to PNU734 (4-bytes) mapped to 0 x 1CAB
Field Name
Example (HEX)
Slave address
01
Function
10
Starting Address HI
1C
Starting Address LO
AB
No. of Registers HI
00
No. of Registers LO
02
Byte count
04
Write Data HI (Register 7339)
00
Write Data LO (Register 7339)
00
Write Data HI (Register 7340)
FF
Write Data LO (Register 7340)
FF
Error Check (CRC)
-
Table 5.1: Request frame
Response
The normal response returns the slave address, function code, starting address, and quantity of registers preset.
Field Name
Example (HEX)
Slave address
01
Function
10
Starting Address HI
1C
Starting Address LO
AB
No. of Registers HI
00
No. of Registers LO
02
Error Check (CRC)
-
Table 5.1: Normal response frame
5 Modbus RTU
VLT
®
Micro Drive FC 51 Operating Instructions
34
MG.02.A4.02 - VLT
®
is a registered Danfoss trademark
5