1.3.7 Power Circuit - Overview

Illustration 1.6 Diagram Showing all Electrical Terminals

* Brake (BR+ and BR-) are not applicable for frame M1.

Brake resistors are available from Danfoss.
Improved power factor and EMC performance can be
achieved by installing optional Danfoss line filters.
Danfoss power filters can also be used for load sharing.

1.3.8 Load Sharing/Brake

Use 6.3 mm insulated Faston Plugs designed for high
voltage for DC (Load Sharing and brake).
Contact Danfoss or see 

instruction MI50N

 for load sharing

and 

instruction MI90F

 for brake.

Load sharing: Connect terminals -UDC and +UDC/+BR.
Brake: Connect terminals -BR and +UDC/+BR (Not
applicable for frame M1).

NOTE

Voltage levels of up to 850 V DC may occur between
terminals
+UDC/+BR and -UDC. Not short circuit protected.

Quick Guide

VLT

®

 Micro Drive Quick Guide

8

MG02B702 - VLT

®

 is a registered Danfoss trademark

1

1

Содержание VLT Micro Drive FC 51 Series

Страница 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT Micro Drive...

Страница 2: ...4 1 3 5 Connecting to Mains and Motor 6 1 3 6 Control Terminals 6 1 3 7 Power Circuit Overview 8 1 3 8 Load Sharing Brake 8 1 4 Programming 9 1 4 1 Programming with LCP 9 1 7 Specifications 14 1 8 Ge...

Страница 3: ...uency switching at high power This will generate a leakage current in the earth connection A fault current in the frequency converter at the output power terminals might contain a DC component which c...

Страница 4: ...ed Start While the frequency converter is connected to mains the motor can be started stopped using digital commands bus commands references or via the LCP Disconnect the frequency converter from main...

Страница 5: ...5 140 248 9 5 1 For with potentiometer add 7 6 mm Table 1 4 Mechanical Dimensions 1 3 3 Electrical Installation in General NOTE All cabling must comply with national and local regulations on cable cro...

Страница 6: ...ation FC 51 Max Fuses UL Max fuses non UL Bussmann Bussmann Bussmann Littel fuse Ferraz Shawmut Ferraz Shawmut 1X200 240 V kW Type RK1 Type J Type T Type RK1 Type CC Type RK1 Type gG 0K18 0K37 KTN R15...

Страница 7: ...hten Illustration 1 2 Mounting of Earth Cable Mains and Motor Wires 1 3 6 Control Terminals All control cable terminals are located underneath the terminal cover in front of the frequency converter Re...

Страница 8: ...Illustration 1 5 Overview of Control Terminals in PNP configuration and Factory Setting Quick Guide VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss trademark 7 1 1...

Страница 9: ...sharing 1 3 8 Load Sharing Brake Use 6 3 mm insulated Faston Plugs designed for high voltage for DC Load Sharing and brake Contact Danfoss or see instruction MI50N for load sharing and instruction MI...

Страница 10: ...ccepting changes to parameter settings Pressing OK for more than 1 s enters Adjust mode In Adjust mode it is possible to make fast adjustment by pressing combined with OK Press to change value Press O...

Страница 11: ...0 199 100 1 62 Slip Compensation 400 399 100 1 63 Slip Compensation Time Constant 0 05 5 00 s 0 10 s 1 7 Start Adjustments 1 71 Start Delay 0 0 10 0 s 0 0 s 1 72 Start Function 0 DC hold delay time 1...

Страница 12: ...f Delay Relay 0 00 600 00 s 0 01 s 5 5 Pulse Input 5 55 Terminal 33 Low Frequency 20 4999 Hz 20 Hz 5 56 Terminal 33 High Frequency 21 5000 Hz 5000 Hz 5 57 Term 33 Low Ref Feedb Value 4999 4999 0 000 5...

Страница 13: ...40 Logic Rule Boolean 1 See par 13 01 0 False 30 32 SL Time out 0 2 13 41 Logic Rule Operator 1 0 Disabled 1 And 2 Or 3 And not 4 Or not 5 Not and 6 Not or 7 Not and not 8 Not or not 13 42 Logic Rule...

Страница 14: ...nnected working 29 Power board over temp X X X Heat sink cut out temperature has been reached 30 Motor phase U missing X X Motor phase U is missing Check the phase 31 Motor phase V missing X X Motor p...

Страница 15: ...3x200 240 V AC 1 At rated load conditions 1 7 2 Mains Supply 3x200 240 V AC Normal overload 150 for 1 min Typical Shaft Output kW PK25 0 25 PK37 0 37 PK75 0 75 P1K5 1 5 P2K2 2 2 P3K7 3 7 Typical Shaft...

Страница 16: ...ns Supply 3x380 480 V AC 1 At rated load conditions Normal overload 150 for 1 minute Frequency converter Typical Shaft Output kW P5K5 5 5 P7K5 7 5 P11K 11 P15K 15 P18K 18 5 P22K 22 Typical Shaft Outpu...

Страница 17: ...ering not more than 100 000 RMS symmetrical Amperes 240 480 V maximum Motor output U V W Output voltage 0 100 of supply voltage Output frequency 0 200 Hz VVCplus 0 400 Hz u f Switching on output Unlim...

Страница 18: ...lay output Programmable relay output 1 Relay 01 Terminal number 01 03 break 01 02 make Max terminal load AC 1 1 on 01 02 NO Resistive load 250 V AC 2 A Max terminal load AC 15 1 on 01 02 NO Inductive...

Страница 19: ...the max ambient temperature If the frequency converter is operated at high ambient temperature the continuous output current should be decreased The frequency converter has been designed for operation...

Страница 20: ...e spare parts kits 132B0129 M4 frame spare parts kits 132B0130 M5 frame spare parts kits 132B0131 Blank cover 130B2522 MCC 107 filter for 132F0001 130B2522 MCC 107 filter for 132F0002 130B2533 MCC 107...

Страница 21: ...g 2 H Hand Mode 11 I IP21 19 Isolated Mains Source 3 IT Mains 3 L Load Compensation 10 Sharing Brake 8 M Main Menu 9 Mains Supply 14 Supply L1 L L2 L3 N 16 Supply 3x200 240 V AC 14 Supply 3x380 480 V...

Страница 22: ...istor 10 U UL Compliance 5 V VLT Control Panel LCP 11 19 Control Panel LCP 12 19 Voltage Level 16 W Warnings And Alarms 13 Index VLT Micro Drive Quick Guide MG02B702 VLT is a registered Danfoss tradem...