7 Troubleshooting
7.1.1 Step-by-step Troubleshooting
Check: LEDs
The option contains two LEDs to indicate the state of the device and the network. During normal operation the MS and at
least one NS LED will show a constant green light.
State
LED
Description
Standby
Green:
Flashing green
The device needs commissioning
Device operational
Green:
Solid green
The device is operational
Major recoverable fault
Flashing red
The device has detected a recoverable fault (MAR)
Major unrecoverable
fault
Red:
Solid red
The device has detected a un-recoverable fault
(MAU)
Self test
Red:
Flashing red/
green
The EIP option is in self-test mode
Green:
Table 7.1 MS: Module Status
State
LED
Description
No connections
Green:
Flashing green
There are no established any CIP connections to
the device
Connected
Green:
Solid green
There is established (at least) one CIP connection to
the device
Connection time-out
Red:
Flashing red
One or more CIP connections has timed-out
Duplicate IP
Red:
Solid red
The IP-address assigned to the device is already in
use
Self test
Red:
Flashing red/
green
The EIP option is in self-test mode
Green
Table 7.2 NS1 + NS2: Network Status (one per port)
Check: Link Status
The status of the Ethernet link cannot be directly identified by means of the LEDs, if no CIP connection is established.
Use
12-10 Link Status
to verify presents of the link.
Use
to verify that the link is steady present.
The parameter will show the duration of the present link, and preset to 00:00:00:00 if the link is broken.
Check: Cabling
In rare cases of cabling mis-configuration, the option might show the presents of a link, but no communication is running.
Exchange the cable in doubt.
Check: IP Address
Verify that the option has a valid IP address (please refer to section: IP Settings) in
12-01 IP Address
. If the option has
identified a duplicate IP Address NS LEDs will light steady red. If the option is set up for BOOTP or DHCP, verify that a
BOOTP or DHCP server is connected in
12-04 DHCP Server
. If no server is connected, the parameter will show:
000.000.000.000.
7.1.2 Alarm Word and Warning Word
Alarm word and warning word are shown in the display in Hex format. If there is more than one warning or alarm, a sum of
all warnings or alarms will be shown. Warning word and alarm word are displayed in
16-90 Alarm Word
to
16-95 Ext. Status
Word 2
. For more information on the individual alarms and warnings, please refer to the frequency converter Design Guide.
Troubleshooting
MCA 121 EtherNet/IP
38
MG.90.J3.02 - VLT
®
is a registered Danfoss trademark
7
7