1.
2.
3.
4.
-
e3
0b
h5
25
.1
0
Illustration 81: Assigning the Device Name
6.13.7 Creating a Sync Domain
A sync domain is a group of PROFINET
®
devices synchronized to a common cycle clock. One device has the role of the sync master
(clock generator). All other devices are sync slaves.
N O T I C E
All devices that exchange data via Isochronous Real-Time (IRT) must belong to the same sync domain.
Procedure
Open the
HW Config
tool.
Select the station with the PROFINET
®
devices to be involved in IRT communication.
Select the PROFINET
®
I/O interface in the section
Station/IO system
.
Select the menu [Edit
→
PROFINET IO
→
Domain management].
AQ262449648484en-000101 / 175R1135 | 113
Danfoss A/S © 2020.08
Commissioning
VLT® Servo Drive System ISD 510/DSD 510
Operating Guide