NOTE
Automatic reset will also be active for resetting safe stop
function.
14-21 Automatic Restart Time
Range:
Function:
10.0 s
*
[0.0 - 600.0 s] Enter the time interval from trip to start of
the automatic reset function. This
parameter is active when
is set to
Automatic reset
[1] - [13].
14-22 Operation Mode
Option:
Function:
Select Initialisation[2] to reset all parameter
values to default.
[0]
*
Normal
operation
Select
Normal operation
[0] for normal
operation of the frequency converter with the
motor in the selected application.
[2]
Initialisation Select
Initialisation
[2] to reset all parameter
values to default settings, except for
,
and
. The frequency converter will
reset during the next power-up.
will also revert to the
default setting
Normal operation
[0].
14-27 Action At Inverter Fault
Option:
Function:
Select how the frequency converter should react at
inverter fault. Action At Inverter Fault
[0]
Trip
[1]
*
Warning
3.10.4 14-4*Energy Optimising
Parameters for adjusting the energy optimisation level in
both Variable Torque (VT) and Automatic Energy Optimi-
zation (AEO) mode.
Automatic Energy Optimization is only active if
, is set for
Auto Energy Optim.
[3].
14-40 VT Level
Range:
Function:
90 %
*
[40 - 90
%]
Enter the level of motor magnetisation at low
speed. Selection of a low value reduces energy
loss in the motor, but also reduces load
capability.
This parameter cannot be adjusted while the
motor is running.
14-41 AEO Minimum Magnetisation
Range:
Function:
66 %
*
[40 - 75 %] Enter the minimum allowable magnetisation
for AEO. Selection of a low value reduces
energy loss in the motor, but can also reduce
resistance to sudden load changes.
3.10.5 14-5* Environment
These parameters help the frequency converter to operate
under special environmental conditions.
14-50 RFI Filter
Option: Function:
[0]
Off Select
Off
[0] only if the frequency converter is fed by an
isolated mains source (IT mains).
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
[1]
*
On Select
On
[1] to ensure that the frequency converter
complies with EMC standards.
14-51 DC-Link Voltage Compensation
Option:
Function:
[0]
Off
Disables DC Link Compensation.
[1]
*
On
Enables DC Link Compensation.
14-52 Fan Control
Option:
Function:
Only valid for the following frequency
converters: 380-480V, 30-90kW.
[0]
*
Auto
[4]
Auto Low Temp Env.
14-53 Fan Monitor
Option:
Function:
Select which reaction the frequency converter
should take in case a fan fault is detected. (Only
valid for some drive sizes.)
[0]
Disabled
[1]
*
Warning
[2]
Trip
14-55 Output Filter
Option:
Function:
Select wether a output filter
is present.
[0]
*
No Filter
[1]
Sine-Wave Filter
[3]
Sine-Wave Filter with Feedback
Parameters
VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark