3.9 Main Menu - Smart Logic - Group 13
3.9.1 13-** Prog. Features
Smart Logic Control (SLC) is essentially a sequence of user
defined actions (see
[x]) executed
by the SLC when the associated user defined
event
(see
[x]) is evaluated as TRUE by the SLC.
Events and
actions
are each numbered and linked together
in pairs. This means that when
event
[0] is fulfilled (attains the
value TRUE),
action
[0] is executed. After this, the conditions
of
event
[1] will be evaluated and if evaluated TRUE,
action
[1]
will be executed and so on. Only one
event
will be evaluated
at any time. If an
event
is evaluated as FALSE, nothing
happens (in the SLC) during the current scan interval and no
other
events
will be evaluated. This means that when the SLC
starts, it evaluates
event
[0] (and only
event
[0]) each scan
interval. Only when
event
[0] is evaluated TRUE, will the SLC
execute
action
[0] and start evaluating
event
[1]. It is possible
to programme from 1 to 20
events
and
actions
. When the last
event
/
action
have been executed, the sequence starts over
again from
event
[0]/
action
[0].
130BA062.13
State 1
Event 1/
Action 1
State 2
Event 2/
Action 2
Start
event P13-01
State 3
Event 3/
Action 3
State 4
Event 4/
Action 4
Stop
event P13-02
Stop
event P13-02
Stop
event P13-02
Illustration 3.1 Example with three event/actions
Starting and stopping the SLC:
Starting and stopping the SLC can be done by selecting
On
[1] or
Off
[0] in
. The SLC always starts
in state 0 (where it evaluates
event
[0]). The SLC starts when
the Start Event (defined in
) is evaluated as
TRUE (provided that
On
[1] is selected in
). The SLC stops when the
Stop Event
is TRUE.
resets all SLC parameters and starts
programming from scratch.
3.9.2 13-0* SLC Settings
Use the SLC settings to activate, deactivate and reset the
Smart Logic Control sequence. The logic functions and
comparators are always running in the background, which
opens for separate control of digital inputs and outputs. .
13-00 SL Controller Mode
Option: Function:
Select On [1] to enable the Smart Logic Control to start
when a start command is present, e.g. via a digital input.
Select Off [0] to disable the Smart Logic Control.
[0] Off Disables the Smart Logic Controller.
[1] On Enables the Smart Logic Controller.
13-01 Start Event
Option:
Function:
Select the boolean (TRUE or FALSE) input
to activate Smart Logic Control.
[0]
False
Enters the fixed value of FALSE in the
logic rule.
[1]
True
Enters the fixed value TRUE in the logic
rule.
[2]
Running
The motor is running.
[3]
In range
Motor runs within programmed current
ranges (
and
[4]
On reference
The motor runs at reference speed.
[7]
Out of current
range
The motor current is outside the range
set in
[8]
Below I low
The motor current is lower than set in
[9]
Above I high
The motor current is higher than set in
[16]
Thermal warning The thermal warning turns on when the
temperature exeeds the limit in the
motor, the frequency converter or the
thermistor.
[17]
Mains out of
range
[18]
Reversing
The frequency converter is reversing.
[19]
Warning
A warning is present.
[20]
Alarm (trip)
An alarm is present.
[21]
Alarm (trip lock)
A trip lock alarm is present.
[22]
Comparator 0
Use the result of comparator 0 in the
logic rule.
[23]
Comparator 1
Use the result of comparator 1 in the
logic rule.
[24]
Comparator 2
Use the result of comparator 2 in the
logic rule.
Parameters
VLT HVAC Basic Drive Programming Guide
50
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Basic Drive...
Страница 98: ...www danfoss com drives MG18B102 130R0221 MG18B102 Rev 2010 07 21...
Страница 99: ......