Terminal Description
Digital Inputs/Outputs
Terminal Parameter
Default
Setting
Description
12, 13
-
+24 V DC
24 V DC supply
voltage. Maximum
output current is 200
mA total for all 24 V
loads. Useable for
digital inputs and
external transducers.
18
5-10
[8] Start
Digital inputs.
19
5-11
[0] No
operation
32
5-14
[0] No
operation
33
5-15
[0] No
operation
27
5-12
[2] Coast
inverse
Selectable for either
digital input or
output. Default setting
is input.
29
5-13
[14] JOG
20
-
Common for digital
inputs and 0 V
potential for 24 V
supply.
37
-
Safe Torque
Off (STO)
(optional) Safe input.
Used for STO
Analog Inputs/Outputs
39
-
Common for analog
output
42
6-50
Speed 0-High
Limit
Programmable analog
output. The analog
signal is 0-20 mA or
4-20 mA at a
maximum of 500
Ω
50
-
+10 V DC
10 V DC analog
supply voltage. 15 mA
maximum commonly
used for potenti-
ometer or thermistor.
53
6-1
Reference
Analog input.
Selectable for voltage
or current. Switches
A53 and A54 select
mA or V.
54
6-2
Feedback
55
-
Common for analog
input
Serial Communication
61
-
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
when experiencing
EMC problems.
Terminal Description
Digital Inputs/Outputs
Terminal Parameter
Default
Setting
Description
68 (+)
8-3
RS-485 Interface. A
control card switch is
provided for
termination resistance.
69 (-)
8-3
Relays
01, 02, 03
5-40 [0]
[0] Alarm
Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.
04, 05, 06
5-40 [1]
[0] Running
Table 2.4 Terminal Description
2.4.5.3 Wiring to Control Terminals
Control terminal connectors can be unplugged from the
frequency converter for ease of installation, as shown in
130B
T306.10
Illustration 2.16 Unplugging Control Terminals
1.
Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in
2.
Insert the bared control wire into the contact.
3.
Remove the screwdriver to fasten the control wire
into the contact.
4.
Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
See
10.1 Power-dependent Specifications
for control terminal
wiring sizes.
See
for typical control wiring
connections.
Installation
VLT
®
HVAC Drive Operating Instructions
18
MG11AH02 - VLT
®
is a registered Danfoss trademark
2
2