1-20 Motor Power [kW]
Range:
Function:
Application
dependent*
[Application dependant]
Enter the nominal motor power in kW according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. Depending on the choices made in
par. 0-03
Regional Settings
, either par. 1-20
or par. 1-21
made invisible.
1-21 Motor Power [HP]
Range:
Function:
Application
dependent*
[Application dependant]
Enter the nominal motor power in HP according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in par. 0-03
Regional Settings
, either par. 1-20
is made invisible.
1-22 Motor Voltage
Range:
Function:
Application
dependent*
[Application dependant]
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
1-23 Motor Frequency
Range:
Function:
Application
dependent*
[20 - 1000 Hz]
NOTE!
This parameter cannot be adjusted while the motor is running.
1-24 Motor Current
Range:
Function:
Application
dependent*
[Application dependant]
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection, etc.
NOTE!
This parameter cannot be adjusted while the motor is running.