Parameter
Option/range
Default
Usage
[20] 440–480 V/50 Hz/IT-grid
[21] 440–480 V/50 Hz/Delta
[22] 440–480 V/50 Hz
[30] 525–600 V/50 Hz/IT-grid
[31] 525–600 V/50 Hz/Delta
[32] 525–600 V/50 Hz
[100] 200–240 V/60 Hz/IT-grid
[101] 200–240 V/60 Hz/Delta
[102] 200–240 V/60 Hz
[110] 380–440 V/60 Hz/IT-grid
[111] 380–440 V/60 Hz/Delta
[112] 380–440 V/60 Hz
[120] 440–480 V/60 Hz/IT-grid
[121] 440–480 V/60 Hz/Delta
[122] 440–480 V/60 Hz
[130] 525–600 V/60 Hz/IT-grid
[131] 525–600 V/60 Hz/Delta
[132] 525–600 V/60 Hz
Parameter 1-10
Motor Con-
struction
*[0] Asynchron
[1] PM, non-salient SPM
[3] PM, salient IPM
[0] Asynchron
Setting the parameter value might change these parame-
ters:
Parameter 1-01 Motor Control Principle
.
Parameter 1-03 Torque Characteristics
.
Parameter 1-08 Motor Control Bandwidth
.
Parameter 1-14 Damping Gain
.
Parameter 1-15 Low Speed Filter Time Const
.
Parameter 1-16 High Speed Filter Time Const
.
Parameter 1-17 Voltage Filter Time Const
.
Parameter 1-20 Motor Power
.
Parameter 1-22 Motor Voltage
.
Parameter 1-23 Motor Frequency
.
Parameter 1-24 Motor Current
.
Parameter 1-25 Motor Nominal Speed
.
Parameter 1-26 Motor Cont. Rated Torque
.
Parameter 1-30 Stator Resistance (Rs)
.
Parameter 1-33 Stator Leakage Reactance (X1)
.
Parameter 1-35 Main Reactance (Xh)
.
Parameter 1-37 d-axis Inductance (Ld)
.
Parameter 1-38 q-axis Inductance (Lq)
.
Parameter 1-39 Motor Poles
.
Parameter 1-40 Back EMF at 1000 RPM
.
Parameter 1-44 d-axis Inductance Sat. (LdSat)
.
Parameter 1-45 q-axis Inductance Sat. (LqSat)
.
Parameter 1-46 Position Detection Gain
.
Parameter 1-48 Current at Min Inductance for d-axis
.
Parameter 1-49 Current at Min Inductance for q-axis
.
AQ367426199594en-000101 / 130R0988 | 37
Danfoss A/S © 2021.06
Programming
VLT® HVAC Drive FC 131
Operating Guide