6.4 Configuring the Drive System
Before the drive system is fully functional, it is necessary to
configure the unit on the local control panel (LCP). The
top-level drive system label is needed for the following
steps. Refer to
1.
Apply power. At power-up, the LCP display shows
alarm 250, New spare part
.
2.
Press [Main Menu] twice on the LCP. See
3.
Press the navigation keys and the [OK] key to
navigate to
parameter group 14-** Special
Functions
. Then scroll down to
parameter 14-23 Typecode Setting
.
4.
Scroll through the submenu to match the 39
characters in the typecode to the 20 index
groups. See
. Press [OK] to enter the
value.
5.
At index number 20, select Save to EEPROM and
press [OK]. When the system finishes writing the
EEPROM data, the display shows
No Function
.
6.
Remove power to the drive system, and then
reapply power. Press [RESET] to clear the alarm.
NOTICE
INCORRECT TYPECODE ENTERED
If the wrong typecode is entered, scroll to
parameter 14-29 Service Code
and enter 00006100. This
step allows access to
parameter 14-23 Typecode Setting
to
reenter the typecode.
130BE712.10
Auto
on
Reset
Hand
on
Off
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Canc
el
In
fo
OK
On
Alarm
Warn.
1
3
2
1
LCP display
2
[Main Menu] key
3
Power-on indicator light
Illustration 6.1 Local Control Panel (LCP)
Index Description
Typecode units
[0]
Product group
1–3
[1]
Series
4–6
[2]
Power
7–10
[3]
Voltage
11–12
[4]
Enclosure
13–15
[5]
RFI filter
16–17
[6]
Brake & stop
18
[7]
Display
19
[8]
Coating
20
[9]
Mains options
21
[10]
Adaptation A
22
[11]
Adaptation B
23
[12]
Software
24–27
[13]
Language
28
[14]
Options A
29–30
[15]
Options B
31–32
[16]
Options C0
33–34
[17]
Options C1
35
[18]
Options C
36–37
[19]
Options D
38–39
Table 6.2 Typecode Index
Initial Start-up
Installation Guide
MG37K302