1-17 Voltage filter time const.
x
1-20 Motor Power [kW]
x
1-22 Motor Voltage
x
1-23 Motor Frequency
x
1-24 Motor Current
x
x
1-25 Motor Nominal Speed
x
x
x
x
1-29 Automatic Motor Adaption
(AMA)
x
x
1-30 Stator Resistance (Rs)
x
x
1-33 Stator Leakage Reactance (X1)
x
1-35 Main Reactance (Xh)
x
1-37 d-axis Inductance (Ld)
x
1-39 Motor Poles
x
x
1-40 Back EMF at 1000 RPM
x
1-52 Min Speed Normal
Magnetising [Hz]
x
1-60 Low Speed Load Compen-
sation
x
1-61 High Speed Load Compen-
sation
x
1-62 Slip Compensation
x
1-63 Slip Compensation Time
Constant
x
1-64 Resonance Dampening
x
1-65 Resonance Dampening Time
Constant
x
1-66 Min. Current at Low Speed
x
1-71 Start Delay
x
x
1-72 Start Function
x
x
1-73 Flying Start
x
x
1-80 Function at Stop
x
x
1-82 Min Speed for Function at
Stop [Hz]
x
x
x
x
1-93 Thermistor Source
x
x
2-00 DC Hold Current
x
2-01 DC Brake Current
x
2-02 DC Braking Time
x
2-04 DC Brake Cut In Speed [Hz]
x
2-06 Parking Current
x
x
2-10 Brake Function
x
x
2-16 AC brake Max. Current
x
2-17 Over-voltage Control
x
4-10 Motor Speed Direction
x
x
4-12 Motor Speed Low Limit [Hz]
x
x
4-14 Motor Speed High Limit [Hz]
x
x
4-18 Current Limit
x
x
4-19 Max Output Frequency
x
x
4-58 Missing Motor Phase Function
x
14-40 VT Level
x
14-41 AEO Minimum Magnetisation
x
Table 3.2 Active Parameters
1-10 Motor Construction
Select the motor construction type. Other parameters will be
changed when changing motor type selection
Option:
Function:
[0]
*
Asynchron
For asynchronous motors.
[1]
PM, non salient
SPM
For permanent magnet (PM) motors with
surface mounted (non salient) magnets.
Refer to parameters 1-14 to 1-17 for
optimising the motor operation
NOTICE
Motor construction can either be asynchronous or
permanent magnet (PM) motor, non-salient SPM.
3.2.3 1-14 to 1-17 VVC
plus
PM
The default control parameters for VVC
plus
PMSM control
core are optimised for HVAC applications and inertia load
in range of 50>Jl/Jm>5, were Jl is load inertia from the
application and jm is machine inertia.
For low inertia applications Jl/Jm<5 it is recommended
that
1-17 Voltage filter time const.
is increased with a factor
of 5-10 and in some cases
1-14 Damping Gain
should also
be reduced to improve performance and stability.
For high inertia applications Jl/Jm>50 it is recommended
that
1-15 Low Speed Filter Time Const.
,
1-16 High Speed Filter
Time Const.
and
1-14 Damping Gain
are increased to
improve performance and stability.
For high load at low speed [<30% of rated speed] it is
recommended that
1-17 Voltage filter time const.
is
increased due to nonlinearity in the inverter at low speed.
1-14 Damping Gain
Range:
Function:
120
%
*
[ 0 -
250
%]
The parameter stabilises the PM motor to ensure
smooth and stable operation. The value of
damping gain controls the dynamic performance
of the PM motor. Low damping gain results in
high dynamic performance and a high value
results in a low dynamic performance. The
dynamic performance is related to the motor data
and load type. If the damping gain is too high or
low, the control becomes unstable.
1-15 Low Speed Filter Time Const
Range:
Function:
Size related
*
[ 0.01 -
20 s]
High pass-filter damping time constant
determines the response time to load
steps. Obtain quick control through a
short damping time constant. However, if
this value is too short, the control gets
unstable. This time constant is used
below 10% rated speed.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02