1-16 High Speed Filter Time Const
Range:
Function:
Size related
*
[ 0.01 -
20 s]
High pass-filter damping time constant
determines the response time to load
steps. Obtain quick control through a
short damping time constant. However, if
this value is too short, the control gets
unstable. This time constant is used
above 10% rated speed.
1-17 Voltage filter time const
Range:
Function:
Size
related
*
[ 0.01 -
1 s]
Machine Supply Voltage Filter Time
constant is used for reducing the
influence of high frequency ripples and
system resonances in the calculation of
machine supply voltage. Without this
filter, the ripples in the currents can
distort the calculated voltage and affects
the stability of the system.
3.2.4 1-2* Motor Data
This parameter group comprises input data from the
nameplate on the connected motor.
NOTICE
Changing the value of these parameters
affects the setting of other parameters.
1-20 Motor Power
Range:
Function:
[2]
0.12 kW - 0.16 hp
[3]
0.18 kW - 0.25 hp
[4]
0.25 kW - 0.33 hp
[5]
0.37 kW - 0.5 hp
[6]
0.55 kW - 0.75 hp
[7]
0.75 kW - 1 hp
[8]
1.1 kW - 1 hp
[9]
1.5 kW - 2 hp
[10]
2.2 kW - 3 hp
[11]
3 kW - 4 hp
[12]
3.7 kW - 5 hp
[13]
4 kW - 5.4 hp
[14]
5.5 kW - 7.5 hp
[15]
7.5 kW - 10 hp
[16]
11 kW - 15 hp
[17]
15 kW - 20 hp
[18]
18.5 kW - 25 hp
[19]
22 kW - 30 hp
[20]
30 kW - 40 hp
[21]
37 kW - 50 hp
[22]
45 kW - 60 hp
1-20 Motor Power
Range:
Function:
[23]
55 kW - 75 hp
[24]
75 kW - 100 hp
[25]
90 kW - 120 hp
[26]
110 kW - 150 hp
1-22 Motor Voltage
Range:
Function:
Size related
*
[ 50.0 -
1000.0 V]
Enter the nominal motor voltage
according to the motor nameplate
data. The default value corresponds to
the nominal rated output of the unit.
1-23 Motor Frequency
Range:
Function:
Size
related
*
[ 20 -
400
Hz]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the motor frequency value from the
motor nameplate data. For 87 Hz operation
with 230/400 V motors, set the nameplate
data for 230 V/50 Hz. Adapt
and
to the 87 Hz application.
1-24 Motor Current
Range:
Function:
Size related
*
[ 0.01 -
26.0 A]
Enter the nominal motor current value
from the motor nameplate data. This
data is used for calculating motor
torque, motor thermal protection etc.
1-25 Motor Nominal Speed
Range:
Function:
Size related
*
[100 -
60000 RPM]
Enter the nominal motor speed value
from the motor nameplate data. This
data is used for calculating automatic
motor compensations.
1-26 Motor Cont. Rated Torque
Range:
Function:
Size related
*
[0.1 -
10000
Nm]
NOTICE
Changing this parameter affects
settings of other parameters.
This parameter is available only when
1-10 Motor Construction
is set to
[1] PM,
non-salient SPM
.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
26
MG18B302 - Rev. 2013-09-02
3
3