Use the semi-automatic bypass speed setup to facilitate the programming of the frequencies to be skipped due to resonances in
the system.
Table 127: Option:
[0]
Off
This function is turned off.
[1]
Enable
If this option is selected, speed ranges are automatically swept to identify bands of resonances.
4.6.4.1 Setting Up Semi-Automatic Bypass Speed
Procedure
Stop the motor.
N O T I C E
Adjust the ramp times in
parameter 3-41 Ramp 1 Ramp Up Time
and
parameter 3-42 Ramp 1 Ramp Down Time
.
Select
[1] Enabled
in
parameter 4-64 Semi-Auto Bypass Set-up
.
Press [Hand On] to start the search for frequency bands causing resonances. The motor ramps up according to the ramp
set.
N O T I C E
Terminal 27 digital input
parameter 5-12 Terminal 27 Digital Input
has
[2] Coast inverse
as default setting. If there is no
24 V to terminal 27, [Hand On] does not start the motor. If so, connect terminal 12 to terminal 27.
When sweeping through a resonance band, press [OK] on the LCP when leaving the band. The actual frequency is stored as
the 1st element in
parameter 4-63 Bypass Speed To [Hz]
(array). Repeat this procedure for each resonance band identified at
the ramp-up (maximum of 3 can be adjusted).
When maximum speed has been reached, the motor automatically begins to ramp down. Repeat this procedure when
speed is leaving the resonance bands during the deceleration. The actual frequencies registered when pressing [OK] are
stored in
parameter 4-61 Bypass Speed From [Hz]
.
When the motor has ramped down to stop, press [OK]. The
parameter 4-64 Semi-Auto Bypass Set-up
automatically resets to
off. The drive stays in hand on mode until [Off] or [Auto On] is pressed.
If the frequencies for a certain resonance band are not registered in the right order (frequency values stored in
parameter 4-63 By-
pass Speed To [Hz]
are ≥ the values in
parameter 4-61 Bypass Speed From [Hz]
), or if they do not have the same numbers of registra-
tions for the
parameter 4-61 Bypass Speed From [Hz]
and
parameter 4-63 Bypass Speed To [Hz]
, all registrations are canceled and the
following message is shown:
Collected speed areas overlapping or not determined. Press [Cancel] to abort
.
4.7 Parameter Group 5-** Digital In/Out
Parameter group for configuration of the digital input and output.
4.7.1 5-0* Digital I/O mode
Parameters for configuring the I/O mode, NPN or PNP, and configuring I/O for Input or Output.
5-00 Digital Input Mode
Default value: [0] PNP
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Set NPN or PNP mode for digital inputs 18, 19, and 27.
Table 128: Option:
[0]
PNP
Action on positive directional pulses (0). PNP systems are pulled down to ground (GND).
[1]
NPN
Action on negative directional pulses (1). NPN systems are pulled up to +24 V internally in the drive.