0-16 Application Selection
Default value: [0] None
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Select an application function from the options. When an application is selected, a set of its related parameters are set automatical-
ly.
N O T I C E
Before selecting an option in
parameter 0-16 Application Selection
, set
[2] Initialisation
for
parameter 14-22 Operation Mode
to en-
sure that all parameter values are reset to default settings.
Table 21: Option:
[0]
None
[12]
Open Loop Control
[13]
Process Closed Loop Control
[14]
Constant Pressure Water Supply
[15]
Multi Pump Control Application
4.2.3 0-3* LCP Custom Readout
Parameters for configuring the custom readout value and defining custom display texts. It is possible to customize the display ele-
ments for various purposes.
Custom readout
The calculated value to be shown is based on settings in
parameter 0-30 Custom Readout Unit
,
parameter 0-31 Custom Readout Min
Value
(linear only),
parameter 0-32 Custom Readout Max Value
,
parameter 4-14 Motor Speed High Limit [Hz]
, and actual speed.
0
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
Liniar
units only
P 0-31
Motor Speed
e3
0b
b7
79
.1
0
Motor Speed
High limit
P 4-14 (Hz)
Lin
ear
Un
it (e
.g.
Spe
ed
and
flo
w)
Qu
ad
rat
ic U
nit
(P
res
sur
e)
Cu
bic
Un
it (
Po
we
r)
Illustration 6: Custom Readout
The relation depends on the type of unit selected in
parameter 0-30 Custom Readout Unit
:
Table 22: Speed Relation
Unit type
Speed relation
Dimensionless
Linear
Speed
Flow, volume
AU363928304090en-000101 / 130R0982 | 35
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide