VLT
®
FCM Series
Programming
Warning word 1
[Hex] indicates one or more warnings
in a Hex code. See page 74 for further information.
Extended status word
[Hex] indicates one or
more status states in a Hex code. See page
74 for further information.
Analog input 1 [mA]
states the signal value on terminal 1.
Analog input 2[V]
states the signal value on terminal 2.
010 Display line 1.1
(DISPLAY LINE 1.1)
Value:
✭
Reference [%]
[1]
See parameter 009.
Function:
This parameter enables a choice of the first of three data
values to be shown on the display, line 1, position 1.
Description of choice:
There is a choice of 24 different data values,
see parameter 009.
011 Display line 1.2
(DISPLAY LINE 1.2)
Value:
✭
Motor current [A]
[1]
See parameter 009
Function:
This parameter enables a choice of the second
of the three data values to be shown on the
display, line 1, position 2.
For Display read-outs, press the [DISPLAY/STATUS]
button, see also page 31.
Description of choice:
There is a choice of 24 different data values,
see parameter 009.
012 Display line 1.3
(DISPLAY LINE 1.3)
Value:
✭
Power [kW]
[8]
See parameter 009
Function:
This parameter enables a choice of the third of the three
data values to be shown on the display, line 1, position 3.
Display read-outs are made by pressing the
[DISPLAY/STATUS] button, see also page 31.
Description of choice:
There is a choice of 24 different data values,
see parameter 009.
013 Local Control/Configuration as
parameter 100
(LOCAL CTRL/CONFIG.)
Value:
Local not active (DISABLE)
[0]
LCP control and open loop.
(LCP CTRL/OPEN LOOP)
[1]
LCP digital control and open loop.
(LCP+DIG CTRL/OP.LOOP)
[2]
LCP control/as parameter 100.
(LCP CTRL/AS P100)
[3]
✭
LCP digital control/as parameter 100.
(LCP+DIG CTRL/AS P100)
[4]
Function:
This is where the desired function is to be selected
if Local control has been chosen in parameter 002.
See also the description of parameter 100.
Description of choice:
If
Local not active
[0] is selected, a possible setting
of
Local reference via parameter
003 is blocked.
It is only possible to change to
Local not active
[0]
from one of the other setting options in parameter
013, when the FC motor has been set to
Remote
control
[0] in parameter 002.
LCP control and open loop
[1] is used when the
speed is to be adjustable (in Hz) via parameter
003, when the FC motor has been set to
Local
control
[1] in parameter 002.
If parameter 100 has not been set to
Speed regulation
open loop
[0], switch to
Speed regulation open loop
[0].
LCP digital control and open loop
[2] functions as
LCP
control and open loop
[1], the only difference being that
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.03.H3.02 - VLT is a registered Danfoss trademark