Programming
All parameters can be programmed in two individual
parameter Setups, Setup 1 and Setup 2. In addition,
there is a pre-programmed Setup, called Factory
Setup, that cannot be modified.
Description of choice:
Factory Setup
[0] contains the factory data. Can
be used as a data source if the other Setups are
to be returned to a known state.
Parameters 005 and 006 allow copying from
one Setup to the other.
Setups 1
[1] and 2 [2] are two individual Setups
that can be selected as required.
Multi-Setup
[5] is used if remote-mounting switching
between Setups is desired. Terminals 2, 3, 4, and
5 as well as the serial communication port can be
used for switching between Setups.
005 Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
✭
Active Setup (ACTIVE SETUP)
[5]
Function:
The choice is of the Setup in which programming
(change of data) is to occur during operation.
It is possible to programme the two Setups
independently of the Setup selected as the Active
Setup (selected in parameter 004).
Description of choice:
The
Factory Setup
[0] contains the factory data and
can be used as a data source if the other Setups
are to be returned to a known state.
Setups 1
[1] and 2 [2] are individual Setups which can
be used as required. They can be programmed freely,
regardless of the Setup selected as the Active Setup
and thus controlling the functions of the FC motor.
NB!:
If a general change of data or a copying to
the Active Setup is effected, this immediately
affects the functioning of the unit.
006 Copying of Setups
(SETUP COPY)
Value:
✭
No copying (NO COPY)
[0]
Copy to Setup 1 from # (COPY TO SETUP 1)
[1]
Copy to Setup 2 from # (COPY TO SETUP 2)
[2]
Copy to Setup all from # (COPY TO ALL)
[5]
# = the Setup selected in parameter 005
Function:
A copy is made from the Setup selected in
parameter 005 to one of the other Setups or to
all the other Setups simultaneously.
NB!:
Copying is only possible in Stop Mode (motor
stopped on a Stop command). Copying will
take max. 3 seconds and has ended when
parameter 006 has returned to value 0.
007 LCP copy
(LCP COPY)
Value:
✭
No copying (NO COPY)
[0]
Upload all parameters (UPLOAD ALL PARAM)
[1]
Download all parameters (DOWNLOAD ALL)
[2]
Download power-independent par.
(DOWNLOAD SIZE INDEP.)
[3]
Function:
Parameter 007 is used if it is desired to use the
integrated copying function of the control panel.
You can therefore easily copy parameter value(s)
from one FC motor to another.
Description of choice:
Select
Upload all parameters
[1] if all parameter
values are to be transmitted to the control panel.
Select
Download all parameters
[2] if all transmitted
parameter values are to be copied to the FC motor
on which the control panel has been mounted.
Select
Download power-independent par.
[3] if
only the power-independent parameters are to be
downloaded. This is used if downloading to a FC
motor that has a different rated power than the one
from where the parameter Setup originates.
NB!:
Uploading/Downloading can only be carried
out in the Stop mode and only between
units with the same major database version
(see par. 626 value major.minor)
✭
= factory setting. () = display text [] = value for use in communication via serial communication port