Make a selection in
8-53 Start Select
to define how Bit 06
Ramp stop/start gates with the corresponding function on
a digital input.
Bit 07, Reset
Bit 07=’0’: No reset.
Bit 07=’1’: Resets a trip. Reset is activated on the signal’s
leading edge, that is, when changing from logic ’0’ to
logic ’1’.
Bit 08, Jog
Bit 08=’1’: The output frequency is determined by
3-11 Jog
Speed [Hz]
.
Bit 09, Selection of ramp 1/2
Bit 09="0": Ramp 1 is active (
3-41 Ramp 1 Ramp Up Time
to
3-42 Ramp 1 Ramp Down Time
).
Bit 09="1": Ramp 2 (
3-51 Ramp 2 Ramp Up Time
to
3-52 Ramp 2 Ramp Down Time
) is active.
Bit 10, Data not valid/Data valid
Tell the frequency converter whether to use or ignore the
control word.
Bit 10=’0’: The control word is ignored.
Bit 10=’1’: The control word is used. This function is
relevant because the telegram always contains the control
word, regardless of the telegram type. Turn off the control
word if not wanting to use it when updating or reading
parameters.
Bit 11, Relay 01
Bit 11="0": Relay not activated.
Bit 11="1": Relay 01 activated provided that
Control word
bit 11=36
is chosen in
5-40 Function Relay
.
Bit 12, Relay 02
Bit 12="0": Relay 02 is not activated.
Bit 12="1": Relay 02 is activated provided that
Control word
bit 12=37
is chosen in
5-40 Function Relay
.
Bit 13, Selection of set-up
Use bit 13 to choose from the 2 menu set-ups according
to the table.
Set-up
Bit 13
1
0
2
1
The function is only possible when
Multi Set-Ups=9
is
selected in
0-10 Active Set-up
.
Make a selection in
8-55 Set-up Select
to define how Bit 13
gates with the corresponding function on the digital
inputs.
Bit 15 Reverse
Bit 15=’0’: No reversing.
Bit 15=’1’: Reversing. In the default setting, reversing is set
to digital in
8-54 Reversing Select
. Bit 15 causes reversing
only when Serial communication, Logic or Logic and is
selected.
3.11.2 Status Word According to FC Profile
(STW) (
8-30 Protocol
= FC profile)
Output freq.
STW
Bit
no.:
Slave-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.10
Illustration 3.13 Status Word
Bit
Bit=0
Bit=1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
No error
Error (no trip)
05
Reserved
-
06
No error
Triplock
07
No warning
Warning
08
Speed
≠
reference
Speed=reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit OK
11
No operation
In operation
12
Drive OK
Stopped, auto start
13
Voltage OK
Voltage exceeded
14
Torque OK
Torque exceeded
15
Timer OK
Timer exceeded
Table 3.35 Status Word According to FC Profile
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00=’0’: The frequency converter trips.
Bit 00=’1’: The frequency converter controls are ready but
the power component does not necessarily receive any
power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready
Bit 01=’1’: The frequency converter is ready for operation
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coasting stop
Bit 02=’0’: The frequency converter releases the motor.
Bit 02=’1’: The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03=’0’ : The frequency converter is not in fault mode.
Bit 03=’1’: The frequency converter trips. To re-establish
operation, press [Reset].
RS-485 Installation and Set...
VLT
®
AutomationDrive FC 360 Design Guide
MG06B202 - VLT
®
is a registered Danfoss trademark
57
3
3
Содержание VLT FC 360
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT AutomationDrive FC 360...
Страница 2: ......
Страница 81: ...Index VLT AutomationDrive FC 360 Design Guide MG06B202 VLT is a registered Danfoss trademark 79...
Страница 82: ...www danfoss com drives MG06B202 130R0499 MG06B202 Rev 2013 03 06...