2.3.4 Internal Current Control in VVC
plus
Mode
The frequency converter features an integral current limit
control which is activated when the motor current, and
thus the torque, is higher than the torque limits set in
4-16 Torque Limit Motor Mode
,
4-17 Torque Limit Generator
Mode
and
4-18 Current Limit
.
When the frequency converter is at the current limit during
motor operation or regenerative operation, the frequency
converter will try to get below the preset torque limits as
quickly as possible without losing control of the motor.
2.3.5 Local (Hand On) and Remote (Auto
On) Control
Operate the frequency converter manually via the local
control panel (LCP) or remotely via analog/digital inputs or
serial bus.
Start and stop the frequency converter pressing the [Hand
On] and [Off/Reset] keys on the LCP. Setup required:
0-40 [Hand on] Key on LCP
,
0-44 [Off/Reset] Key on LCP
, and
0-42 [Auto on] Key on LCP
.
Reset alarms via the [Off/Reset] key or via a digital input,
when the terminal is programmed to "Reset".
Hand
On
Off
Reset
Auto
On
130BB893.10
Illustration 2.3 LCP Control Keys
Local Reference forces the configuration mode to open
loop, independent of the setting of
1-00 Configuration
Mode
.
Local Reference is restored at power-down.
Product Overview
VLT
®
AutomationDrive FC 360 Design Guide
16
MG06B202 - VLT
®
is a registered Danfoss trademark
2
2
Содержание VLT FC 360
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT AutomationDrive FC 360...
Страница 2: ......
Страница 81: ...Index VLT AutomationDrive FC 360 Design Guide MG06B202 VLT is a registered Danfoss trademark 79...
Страница 82: ...www danfoss com drives MG06B202 130R0499 MG06B202 Rev 2013 03 06...