4.1.2 Setting LCP Display Values
The display area is activated when the adjustable
frequency drive receives power from AC line voltage, a DC
bus terminal, or an external 24 V DC supply.
The information displayed on the LCP can be customized
for user application.
•
Each display readout has a parameter associated
with it
•
Options are selected in the quick menu
Q3-13
Display Settings
•
Display 2 has an alternate larger display option
•
The adjustable frequency drive status at the
bottom line of the display is generated automat-
ically and is not selectable
1.1
2
3
1.3
1.2
130B
T831.10
0.0%
Off Remote Stop
1 (1)
0.00 kw
0.00 A
0.0Hz
2605kWh
Status
Figure 4.2 Display Readouts
Display
Parameter number
Default setting
1.1
0-20
Reference %
1.2
0-21
Motor current
1.3
0-22
Power [kW]
2
0-23
Frequency
3
0-24
kWh counter
Table 4.1 Legend to
4.1.3 Display Menu Keys
Menu keys are used for menu access for parameter set-up,
toggling through status display modes during normal
operation, and viewing fault log data.
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
Figure 4.3 Menu Keys
Key
Function
Status
Shows operational information.
•
In Auto mode, press to toggle between
status readout displays.
•
Press repeatedly to scroll through each
status display.
•
Press [Status] plus [
▲
] or [
▼
] to adjust the
display brightness.
•
The symbol in the upper right corner of the
display shows the direction of motor
rotation and which set-up is active. This is
not programmable.
Quick Menu
Allows access to programming parameters for
initial set-up instructions and many detailed
application instructions.
•
Press to access Q2 Quick Set-up for
sequenced instructions to program the basic
adjustable frequency drive set-up
•
Follow the sequence of parameters as
presented for the function set-up
Main Menu
Allows access to all programming parameters.
•
Press twice to access top-level index
•
Press once to return to the last location
accessed.
•
Press to enter a parameter number for
direct access to that parameter.
Alarm Log
Displays a list of current warnings, the last ten
alarms, and the maintenance log.
•
For details about the adjustable frequency
drive before it entered the alarm mode,
select the alarm number using the
navigation keys and press [OK].
Table 4.2 Function Description Menu Keys
User Interface
VLT
®
Refrigeration Drive Instruction Manual
4-2
MG16J122 - VLT
®
is a registered Danfoss trademark
4
4
Содержание VLT FC 103
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT Refrigeration Drive FC 103 75 400 kW ...
Страница 2: ......
Страница 4: ...Safety VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark ...
Страница 8: ...Contents VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark ...
Страница 93: ...Index VLT Refrigeration Drive Instruction Manual MG16J122 VLT is a registered Danfoss trademark 12 5 ...
Страница 94: ...www danfoss com drives MG16J122 130R0414 MG16J122 Rev 2013 04 22 ...