4.1.3 Pulse Start/Stop
Terminal 18 = start/stop
5-10 Terminal 18 Digital Input
[9]
Latched start
Terminal 27= Stop
5-12 Terminal 27 Digital Input
[6]
Stop
inverse
5-10 Terminal 18 Digital Input
=
Latched start
5-12 Terminal 27 Digital Input
=
Stop inverse
195NA432.10
18
13
12
29
27
19
32 33 20
+24V
P 5-10 [9]
P 5-12 [6]
1
3
5
2
4
Illustration 4.3 Pulse Start/Stop
1
Start
2
Stop inverse
3
Speed
4
Start (18)
5
Stop (27)
Table 4.3 Legend for
4.1.4 Potentiometer Reference
Voltage reference via a potentiometer.
3-15 Reference 1 Source
[1] =
Analog Input 53
6-10 Terminal 53 Low Voltage
= 0 V
6-11 Terminal 53 High Voltage
= 10 V
6-14 Terminal 53 Low Ref./Feedb. Value
= 0 RPM
6-15 Terminal 53 High Ref./Feedb. Value
= 1.500
RPM
130BA287.10
55
50
39 42
53 54
Speed RPM
P 6-15
1 kW
+10V/30mA
Ref. voltage
P 6-11 10V
Illustration 4.4 Potentiometer Reference
Application Examples
VLT
®
DriveMotor FCP 106 and FCM 106 Design Guide
36
MG03M102 -
08/2015
4