Register Description
Bits
Details
7
Motor temperature
0–7
Motor 1 thermal model (%).
8–15
Motor 2 thermal model (%).
8
5)
Power
0–11
Power.
12–13 Power scale.
14–15 Reserved.
9
% Power factor
0–7
100% = power factor of 1.
8–15
Reserved.
10
Reserved
0–15
–
11
4)
Current
0–13
Phase 1 current (rms).
14–15 Reserved.
12
4)
Current
0–13
Phase 2 current (rms).
14–15 Reserved.
13
4)
Current
0–13
Phase 3 current (rms).
14–15 Reserved.
14
Reserved
–
–
15
Reserved
–
–
16
Reserved
–
–
17
Parameter list version number
0–7
Parameter list minor revision.
8–15
Parameter list major revision.
18
Digital input state
0–15
For all inputs, 0 = open, 1 = closed (shorted).
0 = Start.
1 = Stop.
2 = Reset.
3 = Input A.
4–15
Reserved.
19–31
Reserved
–
–
Table 7.3 Functions of Internal Registers
1) Product type code: 4=MCD 200, 5=MCD 500.
2) Reading register 3 (changed parameter value) resets registers 2 (changed parameter number) and 4 (parameters have changed). Always read
registers 2 and 4 before reading register 3.
3) Bits 10–15 of register 4 report the soft starter’s trip or warning code. If the value of bits 0–4 is 6, the soft starter has tripped. If bit 5=1, a
warning has activated and the soft starter continues operation.
4) For models MCD5-0053B and smaller, this value is 10 times greater than the value shown on the LCP.
5) Powerscale functions as follows:
0 = Multiply power by 10 to get W.
1 = Multiply power by 100 to get W.
2 = Power is shown in kW.
3 = Multiply power by 10 to get kW.
Packet Structures
Installation Guide
MG17M202
Danfoss A/S © 05/2017 All rights reserved.
17
7
7