4.2 Network Connection
4.2.1 Ethernet Ports
The EtherNet/IP Module has 2 Ethernet ports. If only 1
connection is required, either port can be used.
4.2.2 Cables
Suitable cables for EtherNet/IP Module connection:
•
Category 5
•
Category 5e
•
Category 6
•
Category 6e
4.2.3 EMC Precautions
To minimize electromagnetic interference, Ethernet cables
should be separated from motor and mains cables by
200 mm (7.9 in).
The Ethernet cable must cross the motor and mains cables
at an angle of 90
°
.
1
2
≥ 200 mm
90°
177HA653.10
1
3-phase supply
2
Ethernet cable
Illustration 4.1 Correct Running of Ethernet Cables
4.2.4 Network Establishment
The controller must establish communication directly with
each device before the device can participate in the
network.
4.3 Addressing
Each device in a network is addressed using a MAC
address and an IP address and can be assigned a symbolic
name associated with the MAC address.
•
The module receives a dynamic IP address when
it is connected to the network or can be assigned
a static IP address during configuration.
•
The symbolic name is optional and must be
configured within the device.
•
The MAC address is fixed within the device and is
printed on a label on the front of the module.
ProfiNet
MAC: 00-02-A2-25-DC-B3
1
2
TX/
RX 2
TX/
RX 1
Link 2
Link 1
Er
ror
St
atus
Po
wer
177HA622.10
Illustration 4.2 MAC ID Location
Connection
Installation Guide
MG17M202
Danfoss A/S © 05/2017 All rights reserved.
9
4
4