WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specified
time after power has been removed before performing
service or repair work, could result in death or serious
injury.
1.
Stop the Compressor.
2.
Disconnect the AC mains, permanent magnet
type motors, and remote DC-link power
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
3.
Wait for the capacitors to discharge fully before
performing any service or repair work. The
duration of waiting time is specified in
.
Voltage [V]
Cooling capacity [TR]
Minimum waiting time
(minutes)
3x200
4–6.5
15
3x400
4–5
4
3x400
6.5
15
High voltage may be present even when the warning LED
indicator lights are off.
Table 1.2 Discharge Time
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
•
Ensure the correct grounding of the equipment
by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
•
Ensure that only trained and qualified personnel
perform installation, start up, and maintenance.
•
Ensure that electrical work conforms to national
and local electrical codes.
•
Follow the procedures in these operating
instructions.
WARNING
UNINTENDED MOTOR ROTATION
WINDMILLING
Unintended rotation of permanent magnet motors can
result in serious injury or equipment damage.
•
Ensure that permanent magnet motors are
blocked to prevent unintended rotation.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury, when the frequency converter is not
properly closed.
•
Ensure that all safety covers are in place and
securely fastened before applying power.
1.5 Conventions
•
Numbered lists indicate procedures.
•
Bulleted lists indicate other information.
•
Italicized text indicates the following:
-
Cross-reference
-
Link
-
Parameter name
-
Parameter option
-
Parameter group name
•
All dimensions in drawings are in mm (inch).
•
An asterisk (*) indicates default setting of a
parameter.
1.6 Additional Resources
•
VLT
®
Compressor Drive CDS 803 Operating Guide
entails information on safety, installation and how
to program. It provides a list of warnings and
alarms and general specifications.
•
VLT
®
Compressor Drive CDS 803 Programming
Guide
provides information on how to program
and includes complete parameter descriptions.
•
VLT
®
Compressor Drive CDS 803 Design Guide
entails all technical information about the
frequency converter and customer design and
applications.
•
MCT 10 Set-up Software
enables the user to
configure the frequency converter from a
Windows
™
-based PC environment.
Supplementary publications and manuals are available
from Danfoss. See
and search for
documentation.
Introduction
VLT
®
Compressor Drive CDS 803
4
Danfoss A/S © 06/2019 All rights reserved.
MG18P202
1
1