Control card, 24 V DC output
Terminal number
12, 13
Maximum load
200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
2
Maximum cross-section to relay terminals
2.5 mm
2
(12 AWG)
Minimum cross-section to relay terminals
0.2 mm
2
(30 AWG)
Length of stripped wire
8 mm (0.3 in)
Relay 01 terminal number
1–3 (break), 1–2 (make)
Maximum terminal load (AC-1)
1)
on 1–2 (NO) (Resistive load)
2), 3)
400 V AC, 2 A
Maximum terminal load (AC-15)
1)
on 1–2 (NO) (Inductive load
@
cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 1–2 (NO) (Resistive load)
80 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 1–2 (NO) (Inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
1)
on 1–3 (NC) (Resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
1)
on 1–3 (NC) (Inductive load
@
cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 1–3 (NC) (Resistive load)
50 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 1–3 (NC) (Inductive load)
24 V DC, 0.1 A
Minimum terminal load on 1–3 (NC), 1–2 (NO)
24 V DC 10 mA, 24 V AC 2 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
Relay 02 terminal number
4–6 (break), 4–5 (make)
Maximum terminal load (AC-1)
1)
on 4–5 (NO) (Resistive load)
2), 3)
400 V AC, 2 A
Maximum terminal load (AC-15)
1)
on 4–5 (NO) (Inductive load
@
cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 4–5 (NO) (Resistive load)
80 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 4–5 (NO) (Inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
1)
on 4–6 (NC) (Resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
1)
on 4–6 (NC) (Inductive load
@
cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 4–6 (NC) (Resistive load)
50 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 4–6 (NC) (Inductive load)
24 V DC, 0.1 A
Minimum terminal load on 4–6 (NC), 4–5 (NO)
24 V DC 10 mA, 24 V AC 2 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
1) IEC 60947 part 4 and 5.
2) Overvoltage Category II.
Control card, +10 V DC output
Terminal number
50
Output voltage
10.5 V
±
0.5 V
Maximum load
25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0–1000 Hz
±
0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
≤
2 m/s
Speed control range (open loop)
1:100 of synchronous speed
Speed accuracy (open loop)
30–4000 RPM: Maximum error of
±
8 RPM
All control characteristics are based on a 4-pole asynchronous motor.
Control card performance
Scan interval
5 M/S
Specifications
Design Guide
MG06K102
Danfoss A/S © 03/2019 All rights reserved.
21
5
5
Содержание VLT AutomationDrive FC 361
Страница 2: ......