manualshive.com logo in svg
background image

X2.1–X2.4 Motor Connectors M23 (in M25)
Female

General ratings

Pins 1, 2, 3, and 4: 480 V AC, maximum 15 A.

Pins C and D: 30 V DC, maximum 3 A.

Tightening torque: 1.5–2.0 Nm (13.3–17.7 in-lb).

Pin

Label

Connected to frequency

converter wiring schematic

Minimum

wire [mm

2

(AWG)]

1

U

96 (U)

2.5 (14)

3

V

97 (V)

2.5 (14)

4

W

98 (W)

2.5 (14)

2

PE

99 (PE)

2.5 (14)

Table 4.3 Wire/Connector Assignment for Plug X2

Mating part: Motor X2 (male)
Phoenix ordering number: KCX-K0341/XX,XX
Maximum cable length: 7.0 m (23 ft)

2 Motor Connection Variant (134N3195)

To meet the protection rating, always keep blind plugs
installed.

Label

Connected to frequency converter wiring schematic

X2.1-B

53

X2.2-A

50

X2.1-A and

X2.2-B

Connected to a common terminal

X2.1-C and

X2.2-C

Connected to an open terminal available in the

frequency converter

X2.1-D and

X2.2-D

Connected to an open terminal available in the

frequency converter

Table 4.4 2 Motor Connection

4 Motor Connection Variant (134N3196)

Label

Connected to frequency converter wiring schematic

X2.1-B

53

X2.4-A

50

X2.1-A and

X2.2-B

Connected via an internal terminal

X2.2-A and

X2.3-B

Connected via an internal terminal

X2.3-A and

X2.4-B

Connected via an internal terminal

Table 4.5 4 Motor Connection

X51 PROFIBUS M12 Male, X52 PROFIBUS M12
Female

General ratings

30 V DC, maximum 1 A.

Tightening torque: 0.2–0.3 Nm (1.8–2.7 in-lb)

Label

 

Connected to frequency converter PROFIBUS

connector

1

5  V  DC

67

2

63

3

0  V  DC

66

4

62

Table 4.6 PROFIBUS Connection

Mating part: PROFIBUS X52 and X51 (female/male)
Phoenix ordering number: SAC-2P-MSB/ XX,XX-910/FSB SCO CT

X11–X14 I/O Connector Box (134N3195–
134N3196)

Phoenix sensor/actuator box - SACB-4/4-L-0,57HPUR CDA -
1531426.

Tightening torque sensor/actuator cable: 0.4 Nm (3.5 in-lb).

Label

Wire

Connected to frequency converter

wiring schematic

X11-X14 1

Brown

12

+24 V Out

X11-X14 2

X11-X14 3

Blue

20

COM D IN

X14-4

Gray

33

D IN

X13-4

Yellow

29

D IN/OUT

X12-4

Green

19

D IN

X11-4

White

18

D IN

Table 4.7 Connector Box (134N3195–134N3196)

X11–X14 I/O Connector Box (134N8410)

Phoenix sensor/actuator box - SACB-4/4-L-0,57HPUR CDA -
1531426.

Tightening torque sensor/actuator cable: 0.4 Nm (3.5 in-lb)

Label

Wire

Connected to wiring schematic

X11-X14 1

Brown

Connected to

frequency

converter wiring

schematic

12

+24 V Out

X11-X14 2

X11-X14 3

Blue

20

COM D IN

X14-4

Gray

Connected to C-

option, MCO 305

wiring schematic

X57-4

X13-4

Yellow

X57-3

X12-4

Green

X57-2

X11-4

White

X57-1

Table 4.8 Connector Box (134N8410)

Installation Instructions

VLT® AutomationDrive FC 302 with Connectors

MI04G402

Danfoss A/S © 11/2015 All rights reserved.

3

Отзывы: