Recommended max. fuse
FC 302
Power
Bussmann
Ferraz- Shawmut
Ferraz- Shawmut
Littel fuse
[kW]
JFHR2
J
JFHR2
1)
JFHR2
0.37-1.1
FWH-6
HSJ-6
-
-
1.5-2.2
FWH-10
HSJ-10
-
-
3
FWH-15
HSJ-15
-
-
4
FWH-20
HSJ-20
-
-
5.5
FWH-25
HSJ-25
-
-
7.5
FWH-30
HSJ-30
-
-
11
FWH-40
HSJ-40
-
-
15
FWH-50
HSJ-50
-
-
18
FWH-60
HSJ-60
-
-
22
FWH-80
HSJ-80
-
-
30
FWH-100
HSJ-100
-
-
37
FWH-125
HSJ-125
-
-
45
FWH-150
HSJ-150
-
-
55
FWH-200
HSJ-200
A50-P-225
L50-S-225
75
FWH-250
HSJ-250
A50-P-250
L50-S-250
Table 3.35 380-500 V, Frame Sizes A, B, and C
1)
Ferraz-Shawmut A50QS fuses may substitute for A50P fuses.
Recommended max. fuse
FC 302
Power
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
[kW]
Type RK1
Type J
Type T
Type CC
Type CC
Type CC
0.75-1.1
KTS-R-5
JKS-5
JJS-6
FNQ-R-5
KTK-R-5
LP-CC-5
1.5-2.2
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
3
KTS-R15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
4
KTS-R20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5.5
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
7.5
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
11
KTS-R-35
JKS-35
JJS-35
-
-
-
15
KTS-R-45
JKS-45
JJS-45
-
-
-
18
KTS-R-50
JKS-50
JJS-50
-
-
-
22
KTS-R-60
JKS-60
JJS-60
-
-
-
30
KTS-R-80
JKS-80
JJS-80
-
-
-
37
KTS-R-100
JKS-100
JJS-100
-
-
-
45
KTS-R-125
JKS-125
JJS-125
-
-
-
55
KTS-R-150
JKS-150
JJS-150
-
-
-
75
KTS-R-175
JKS-175
JJS-175
-
-
-
Table 3.36 525-600 V, Frame Sizes A, B, and C
How to Install
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16
65
3
3
Содержание VLT AutomationDrive FC 302
Страница 2: ......