Enclosure
FC 300 power
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max trip level
Size
[kW]
Moeller
[A]
A2
0-75-4.0
gG-10
gG-25
PKZM0-25
25
A3
5.5-7.5
gG-10 (5.5)
gG-16 (7.5)
gG-32
PKZM0-25
25
B3
11-15
gG-25 (11)
gG-32 (15)
gG-63
PKZM4-50
50
B4
18.5-30
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-125
NZMB1-A100
100
C3
37-45
gG-63 (37)
gG-100 (45)
gG-150
NZMB2-A200
150
C4
55-75
aR-160 (55)
aR-200 (75)
aR-250
NZMB2-A250
250
A5
0.75-7.5
gG-10 (0.75-5.5)
gG-16 (7.5)
gG-32
PKZM0-25
25
B1
11-18
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-80
PKZM4-63
63
B2
22-30
gG-50 (22)
gG-63 (30)
gG-100
NZMB1-A100
100
C1
37-55
gG-63 (37)
gG-100 (45)
aR-160 (55)
gG-160 (37-45)
aR-250 (55)
NZMB2-A200
160
C2
75
aR-200 (75)
aR-250
NZMB2-A250
250
Table 3.28 525-600 V, Frame Sizes A, B, and C
How to Install
VLT
®
Automation Drive FC 300 Operating Instructions
60
MG33U402 - Rev. 2013-12-16
3
3
Содержание VLT AutomationDrive FC 302
Страница 2: ......