background image

4.3 X2.1-X2.4 

Motor 

Connectors M23 (in M25)

Female

General ratings

Pins 1, 2, 3 and 4: 480 V AC, maximum 15 A

Pins C and D: 30 V DC, maximum 3 A

Tightening torque: 1.5–2.0 Nm

Pin

Label

Connected to frequency

converter wiring schematic

Min. wire

[mm

2

]

1

U

96  (U)

2.5

3

V

97  (V)

2.5

4

W

98  (W)

2.5

2

PE

95

2.5

Table 4.3 Wire/Connector Assignment for Plug X2

Mating part: Motor X2 (male)
Phoenix order number.: KCX-K0341/XX,XX
Max. cable length 7.0 m

4.4  2 Motor Connection Variant (134N3195)

Keep blind plugs installed at all times to keep the enclosure
tight.

Label

Connected to frequency converter wiring schematic

X2.1-B

53

X2.2-A

50

X2.1-A and

X2.2-B

Connected to a common terminal

X2.1-C and

X2.2-C

Connected to an open terminal available in the

frequency converter

X2.1-D and

X2.2-D

Connected to an open terminal available in the

frequency converter

Table 4.4 2 Motor Connection

4.5  4 Motor Connection Variant (134N3196)

Label

Connected to frequency converter wiring schematic

X2.1-B

53

X2.4-A

50

X2.1-A and

X2.2-B

Connected via an internal terminal

X2.2-A and

X2.3-B

Connected via an internal terminal

X2.3-A and

X2.4-B

Connected via an internal terminal

Table 4.5 4 Motor Connection

4.6  X51 PROFIBUS M12 Male, X52 PROFIBUS

M12 Female

General ratings

30 V DC, maximum 1 A

Tightening torque: 0.2–0.3 Nm

Label

 

Connected to frequency converter PROFIBUS

connector

1

5  V  DC

67

2

 

63

3

0  V  DC

66

4

 

62

Table 4.6 PROFIBUS Connection

Mating part: PROFIBUS X52 and X51 (female/male)
Phoenix order number.: SAC-2P-MSB/ XX,XX-910/FSB SCO CT

4.7  X11-X14 I/O Connector Box

Phoenix sensor/actuator box - SACB-4/4-L-0,57HPUR CDA -
1531426

Tightening torque slot sensor/actuator cable 0.4 Nm

Label

Wire

Connected to frequency

converter wiring schematic

 

X11-X14 1

Brown

12

+24 V Out

X11-X14 2

X11-X14 3

Blue

20

COM D IN

X14-4

Grey

33

D IN

X13-4

Yellow

29

D IN/OUT

X12-4

Green

19

D IN

X11-4

White

18

D IN

Table 4.7 Connector Box

5 Installation

NOTICE

For installation, refer to the 

VLT

®

 AutomationDrive FC 302

Operating Instructions

.

Installation Instructions

VLT® AutomationDrive FC 302 with Connectors

MI04G102

Danfoss A/S © Rev. 06/2014 All rights reserved.

3

Отзывы: