Terminal description
Terminal
Parameter
Default
setting
Description
Serial communication
61
-
Integrated RC filter for
cable shield. ONLY for
connecting the shield
in the event of EMC
problems.
68 (+)
8-3*
RS-485 interface. A
control card switch is
provided for
termination resistance.
69 (-)
8-3*
Relays
01, 02, 03
5-40 [0]
[0] No
operation
Form C relay output.
For AC or DC voltage
and resistive or
inductive loads.
04, 05, 06
5-40 [1]
[0] No
operation
Table 4.3 Terminal Description Serial Communication
Additional terminal:
•
Two form C relay outputs. The location of the
outputs depends on the adjustable frequency
drive configuration.
•
Terminals located on built-in optional equipment.
See the manual provided with the equipment
option.
4.8.2 Wiring to Control Terminals
Control terminal connectors can be unplugged from the
adjustable frequency drive for ease of installation, as
shown in
NOTICE!
Keep control wires as short as possible and separate
from high power cables to minimize interference.
1.
Open the contact by inserting a small screwdriver
into the slot above the contact and push the
screwdriver slightly upwards.
130BD546.10
2
1
10 mm
29
27
32
19
18
13
12
33
Figure 4.9 Connecting Control Wires
2.
Insert the bare control wire into the contact.
3.
Remove the screwdriver to fasten the control wire
into the contact.
4.
Ensure that the contact is firmly established and
not loose. Loose control wiring can be the source
of equipment faults or less than optimal
operation.
See
chapter 8.5 Cable Specifications
for control terminal
wiring sizes and
chapter 6 Application Set-up Examples
for
typical control wiring connections.
4.8.3 Enabling Motor Operation (Terminal
27)
A jumper wire may be required between terminal 12 (or
13) and terminal 27 for the adjustable frequency drive to
operate when using factory default programming values.
•
Digital input terminal 27 is designed to receive
24 V DC external interlock command.
•
When no interlock device is used, wire a jumper
between control terminal 12 (recommended) or
13 to terminal 27. This provides an internal 24 V
signal on terminal 27.
•
When the status line at the bottom of the LCP
reads
AUTO REMOTE COAST
, this indicates that the
unit is ready to operate but is missing an input
signal on terminal 27.
•
When factory installed optional equipment is
wired to terminal 27, do not remove that wiring.
NOTICE!
The adjustable frequency drive cannot operate without a
signal on terminal 27, unless terminal 27 is re-
programmed.
Electrical Installation
Instruction Manual
MG33AP22
Danfoss A/S © Rev. 09/2014 All rights reserved.
19
4
4