Parameter 20-95 PID Differentiation Time
is set to value 0
(zero).
Parameter 20-81 PID Normal/ Inverse Control
is
determined during the tuning process.
These calculated values are presented in the LCP and can
be either accepted or rejected. Once accepted, the values
are written to the relevant parameters and auto-tuning
mode is disabled in
Depending on the system, the time required to carry out
auto-tuning could be several minutes.
Before carrying out the auto-tuning, set the following
parameters according to the load inertia:
•
Parameter 3-41 Ramp 1 Ramp Up Time
•
Parameter 3-42 Ramp 1 Ramp Down Time
Or
•
Parameter 3-51 Ramp 2 Ramp Up Time
•
Parameter 3-52 Ramp 2 Ramp Down Time
If PID auto-tuning is carried out with slow ramp times, the
auto-tuned parameters typically result in slow control.
Before activating PID auto-tuning, remove excessive
feedback sensor noise using the input filter (
parameter
groups
6-** Analog In/Out
,
5-5* Pulse Input
and
26-** Analog
I/O Option MCB 109
,
parameter 6-16 Terminal 53 Filter Time
,
parameter 6-26 Terminal 54 Filter Time Constant
parameter 5-54 Pulse Filter Time Constant #29
,
parameter 5-59 Pulse Filter Time Constant #33
). To obtain the
most accurate controller parameters, carry out PID auto-
tuning when the application runs in typical operation, that
is with a typical load.
SPC Auto-tuning
SPC initiates a tuning of DRC. If feedback from the system
determines the system to be 2
nd
order, auto-tuning
proceeds automatically with tuning of PID parameters. If
SPC discards the DRC, it is shown by the process bar going
to step 4.
DRC assumes that the frequency converter’s target
applications can be generically modeled as 1
st
order plus
dead-time systems. DRC auto-tuning is providing the
feedback for calculation.
•
τ = time constant of process system K
p
process
system gain.
•
θ = time delay between input and output DRC
can only be set up by using SPC.
20-70 Closed Loop Type
Option:
Function:
Select the application response speed if it
is known. The default setting is sufficient
for most applications. A more precise
value decreases the time needed for
carrying out PID adaptation. The setting
has no impact on values of parameters
and only affects the auto-tuning speed.
[0]
*
Auto
Takes 30–120 s to complete.
20-70 Closed Loop Type
Option:
Function:
[1]
Fast Pressure
Takes 10–60 s to complete.
[2]
Slow Pressure
Takes 30–120 s to complete.
[3]
Fast
Temperature
Takes 10–20 minutes to complete.
[4]
Slow
Temperature
Takes 30–60 minutes to complete.
20-71 Controller Performance
Option:
Function:
[0]
*
Normal Normal setting of this parameter is suitable for
pressure control in fan systems.
[1]
Fast
Fast setting is used in pumping systems, where a
faster control response is wanted.
20-72 Output Change
Range:
Function:
0.10
*
[0.01
- 0.50 ]
This parameter sets the magnitude of step
change during auto-tuning. The value is a
percentage of full speed. That is, if maximum
output frequency in
parameter 4-14 Motor Speed High
is set to 50 Hz, 0.10 is 10% of 50 Hz,
which is 5 Hz. Set this parameter to a value
resulting in feedback changes of 10–20% for best
tuning accuracy.
20-73 Minimum Feedback Level
Range:
Function:
-999999
ProcessCtrlUnit
*
[ -999999.999 -
par. 20-74
ProcessCtrlUnit]
Enter the minimum allowable
feedback level in user units as
defined in
parameter 20-12 Reference/
Feedback Unit
. If the level
drops below
parameter 20-73 Minimum
Feedback Level
, auto-tuning is
aborted and an error message
appears in the LCP.
20-74 Maximum Feedback Level
Range:
Function:
999999
ProcessCtrlUnit
*
[ par. 20-73 -
999999.999
ProcessCtrlUnit]
Enter the maximum allowable
feedback level in user units as
defined in
parameter 20-12 Reference/
Feedback Unit
. If the level
rises above
parameter 20-74 Maximum
Feedback Level
, auto-tuning is
aborted and an error message
appears in the LCP.
Parameter Description
VLT
®
AQUA Drive FC 202
166
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3