31
005
Maximum Value of User-Defined Readout
(CUSTOM READOUT )
Value:
0.01 - 999,999.99
✭
100.000
Function:
This parameter determines the value that the user defined meter will
display when the drive’s output frequency is the value set in parameter
202, Output Frequency High.
Description of choice:
Set the required value for maximum output frequency.
006
Unit for User Defined Readout
(CUST. READ. UNIT)
Value:
No unit
1
[0]
GPM
1
[21]
✭
%
1
[1]
gal/s
1
[22]
rpm
1
[2]
gal/min
1
[23]
ppm
1
[3]
gal/h
1
[24]
pulse/s
1
[4]
lb/s
1
[25]
l/s
1
[5]
lb/min
1
[26]
l/min
1
[6]
lb/h
1
[27]
l/h
1
[7]
CFM
1
[28]
kg/s
1
[8]
ft3/s
1
[29]
kg/min
1
[9]
ft3/min
1
[30]
kg/h
1
[10]
ft3/h
1
[31]
m3/s
1
[11]
ft3/min
1
[32]
m3/min
1
[12]
ft/s
1
[33]
m3/h
1
[13]
in wg
2
[34]
m/s
1
[14]
ft wg
2
[35]
mbar
2
[15]
PSI
2
[36]
bar
2
[16]
lb/in
2
[37]
Pa
2
[17]
HP
3
[38]
MPa
2
[18]
MWG
2
[19]
kW
3
[20]
1
Linear units (flow or speed)
2
Squared units (pressure)
3
Cubed units (power)
Function:
Select a unit to be shown with the display of the User Defined Readout.
If flow or speed units are selected, the relationship between readout
and output frequency will be a linear one. If pressure units are
selected, the ratio will be square. If power units are selected, the ratio
will be cubed.
The value and the unit are shown in display mode whenever User
Defined Readout has been selected in one of parameters 007 through
010, Display Readout.
✭
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
Description of choice:
Select the required unit for User Defined Readout.
007
Large Display Readout
(LARGE READOUT)
Value:
Resulting reference [%] (REFERENCE [%])
[1]
Resulting reference [unit] (REFERENCE [UNIT])
[2]
Frequency [Hz] (FREQUENCY [HZ])
[3]
✭
% of maximum output frequency [%]
(FREQUENCY [%])
[4]
Motor current [A] (MOTOR CURRENT [A])
[5]
Power [kW] (POWER [KW])
[6]
Power [HP] (POWER [HP])
[7]
Output energy [kWh] (ENERGY [UNIT])
[8]
Hours run [Hours] (HOURS RUN [h])
[9]
User-defined readout [-]
(CUSTOM READ. [UNITS])
[10]
Setpoint 1 [unit] (SETPOINT 1 [UNITS])
[11]
Setpoint 2 [unit] (SETPOINT 2 [UNITS])
[12]
Feedback 1 (FEEDBACK 1 [UNITS])
[13]
Feedback 2 (FEEDBACK 2 [UNITS])
[14]
Feedback [unit] (FEEDBACK [UNITS])
[15]
Motor voltage [V] (MOTOR VOLTAGE [V])
[16]
DC link voltage [V] (DC VOLTAGE [V])
[17]
Thermal load, motor [%]
(THERM.MOTOR LOAD [%])
[18]
Thermal load, VLT [%] (THERM.DRIVE LOAD [%])
[19]
Digital input [Binary code] (DIGITAL INPUT [BIN])
[20]
Analog input 53 [V] (ANALOG INPUT 53 [V])
[21]
Analog input 54 [V] (ANALOG INPUT 54 [V])
[22]
Analog input 60 [mA] (ANALOG 60 [mA])
[23]
Pulse reference [Hz] (PULSE REFERENCE [Hz])
[24]
External reference [%] (EXT. REFERENCE [%])
[25]
Heat sink temp. [
o
C] (HEATSINK TEMP [
o
C])
[26]
Free programming array (FREE PROG. ARRAY)
[27]