Power up

1. Turn BACLink power switch to OFF. This prevents

BACLink from power up before proper voltage is verified.

2. Ensure that power is applied to the drives.

3. Plug connector from transformer to BACLink 24 VAC

power terminal.

4. Ensure that 24 VAC is present at BACLink power input

terminals.

5. Turn BACLink power switch to ON. Power, Run and Error

LEDs turn on. Run and Error LEDs then begin blinking.
Error LED turns off.

Troubleshooting drive communication

For use in the event of trouble communicating with the drives. Test

conditions for BACLink portal communications:

1. Test only one drive connected to portal at a time.

2. Portal power OFF.

SYMPTOM 

CAUSE 

SOLUTION 

Link LED is OFF. 
Lan LED is OFF. 

• 

Network speed set to 
100kbps. 

• 

BACLink board not 
connected to network 

• 

Portal address not 
set for network or not 
recognized. 

• 

Set network speed for 10kbps. 

• 

Connect board to network. 

• 

Ping portal to test communications. To 
ping portal, go to a DOS prompt on any 
network computer. Type “ping” and the 
portal address (displayed on the IP 
address label on the unit) and press 
enter. If communicating, you will get a 
reply. If not communicating, you will get 
no response indication. 

 

SYMPTOM 

CAUSE 

SOLUTION 

Transmit LED ON steady 
and receive LED OFF. 

Reversed polarity to drive or short in 
EIA-485 cable. 

Reverse wires to drive terminals 68 
(+) and 69 (-) or remove short. 

Transmit LED blinks slowly 3 
times, then pauses and 
repeats 3 blinks. 

• 

Drive not ON. 

• 

Drive not set for N2 protocol in 
parameter 500. 

• 

Drive serial bus address not 
correct in parameter 501. 

• 

Network cable not connected. 

• 

For VLT 6000: termination 
switches on drive in wrong 
position. 

• 

Apply power to drive. 

• 

Set parameter 500 for N2 
protocol. 

• 

Set drive address in 
parameter 501. 

• 

Connect network cable to 
unit. 

• 

Set termination switches 2 
and 3 to ON position. 

 

Table V.  Troubleshooting Drive Communication

Table VI.  Troubleshooting Ethernet Communication

3. For VLT 6000, termination DIP switches 2 and 3 should be

in the ON position. Termination DIP switches are located on

VLT 6000 power board directly above drive terminals
where connections to terminals 68 and 69 are made.

4. Drive power ON.

5. Apply power to portal and wait 20-25 seconds. (See

Table V for test results.)

Troubleshooting Ethernet communication

With the BACLink portal connected to BACnet network through the

Ethernet connector, apply power to BACLink portal and switch
portal ON. See Table VI for test results.

Loss of signal recovery time

When serial communication is lost to the drive, recovery time to

reestablish communication with the network can take up to

5 minutes.

Содержание VLT 6000 series

Страница 1: ...Instruction Manual BACLink VLT 6000 and VLT 2800 Adjustable Frequency Drives 176U7869 10 02...

Страница 2: ...ave fully discharged wait 14 minutes after power has been removed before touching any internal component DANGER Copyright 2002 Danfoss Graham WARNING Warnings Against Unintended Start 1 While the driv...

Страница 3: ...tart up 10 Changing VLT 6000 parameter data 10 VLT 2800 network connection 11 VLT 2800 BACnet start up 11 Changing VLT 2800 parameter data 11 Ethernet network connection 12 Wiring 12 Set IP address of...

Страница 4: ...ints in the N2 database are classified as analog I O floating point binary I O or integer data points Each data type has a unique structure defined in the Metasys N2 system Protocol Specification for...

Страница 5: ...s used to enable selection of IP address module address and network type Sw1 and Sw2 are disabled in VLTcommunication applications Keypad Display port Access port for optional keypad Port 2 Preferred...

Страница 6: ...an enclosure mount the unit in an enclosed panel using the mounting holes provided on the BACLink portal backplate refer back to Figure 1 Leave about 2 inches 5 centimeters on each side for wiring acc...

Страница 7: ...3 BACLink Enclosure Electrical Components Electrical wiring 1 Power must be supplied to the 115 VAC outlet from an external source see Figure 3 2 Plug transformer into 115 VAC outlet 3 Connect transfo...

Страница 8: ...P and terminal 69 N on main control board of drive see figure 5 2 If shielded cabling is used connect one end of shield to terminal 61 This terminal is connected to ground via an internal RC link For...

Страница 9: ...9600 for N2 protocol 503 Coasting LOGIC OR 504 DC brake LOGIC OR 505 Start LOGIC OR 506 Reversing DIGITAL INPUT 507 Select setup LOGIC OR 508 Select speed LOGIC OR 560 Override release time OFF The va...

Страница 10: ...or details on changing parameters and programming the drive The appendix in this manual lists point maps for BACnet Changing VLT 2800 parameter data Use the VLT2800 keypad to access the Menu Mode and...

Страница 11: ...nfiguration jumpers Procedure 1 Wiring Wire Connections Each BACLink portal can support up to 10 drives see Figure 7 Any mix of VLT 2800 or VLT 6000 drives is supported The preferred portal to drive w...

Страница 12: ...the portal network address using the rotary switches 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 10 s digit 1 s digit Figure 8 BACLink DIP Switches Figure 9 Rotary Address Switches C Set BACLink portal a...

Страница 13: ...es see Figure 14 6 Set BACLink portal address DIP switch BACLink portal DIP switch 5 refer back to Figure 1 must correspond to device instance number setting Set switch to 0 for addresses 0 to 99 or t...

Страница 14: ...7 5 Plug EIA 485 configuration jumper to 2 wire position as shown in Figure 17 7 Wire to drives from BACLink port 2 from Net to drive terminal 68 and Net to drive terminal 69 Figure 17 Port 2 Configur...

Страница 15: ...19 4 Plug EIA 485 232 configuration jumper to EIA 232 position as shown in Figure 20 5 Wire to drives from BACLink port 2 from Net to drive terminal 68 and Net to drive terminal 69 EIA 232 network con...

Страница 16: ...n SYMPTOM CAUSE SOLUTION Transmit LED ON steady and receive LED OFF Reversed polarity to drive or short in EIA 485 cable Reverse wires to drive terminals 68 and 69 or remove short Transmit LED blinks...

Страница 17: ...lows resetting drive after a fault that does not require cycling power Reset occurs at transition from OFF to ON 0 Off 1 On jog_ Used to start and run drive at a frequency set in parameter 209 0 Off 1...

Страница 18: ...y vlt6000_prop_gain_ PID proportional gain for VLT 6000 only 0 00 to10 00 423 VLT 6000 only vlt6000_int_time_ PID integration time for VLT 6000 only 0 01 to 9999 00 sec 424 VLT 6000 only vlt6000_fb_fi...

Страница 19: ...r_volt_ VAC Voltage being supplied to motor 517 524 dc_bus_volt_ VDC DC bus voltage of drive 518 525 therm_motor_load_ Calculated thermal load on motor Trip point is 100 519 526 therm_inverter_load_ C...

Страница 20: ...ng 531 540 current_high_ 0 OK 1 Warning 531 540 feedback_low_ 0 OK 1 Warning 531 540 feedback_high_ 0 OK 1 Warning 531 540 live_zero_error_ 0 OK 1 Warning 531 540 phase_loss_ 0 OK 1 Warning 531 540 dr...

Страница 21: ..._32_ 0 Off 1 On for VLT 6000 only 521 VLT 6000 only terminal_29_ 0 Off 1 On for VLT 6000 only 521 VLT 6000 only terminal_27_ 0 Off 1 On for VLT 6000 only 521 VLT 6000 only terminal_19_ 0 Off 1 On for...

Страница 22: ...am Division of Danfoss Inc 8800 West Bradley Road P O Box 245041 Milwaukee Wisconsin 53224 9541 Phone 414 355 8800 Fax 414 355 6117 Toll free 800 621 8806 E mail graham grahamdrives com http www namc...

Отзывы: