13
VLT is a registered Danfoss trademark
Figure 10. Port 2 Configuration Jumpers
NOTE
Steps 2 and 3 in the following connection
procedure may have already been factory-set
based upon customer ordering information.
Default IP address is 192.168.168.xxx.
Default subnet mask is 255.255.255.0.
Default gateway address is 0.0.0.0.
2. Set IP address of portal
A. Set IP address to default or assigned.
The BACLink portal
has either an internal default Internet Protocol (IP) address or a
factory-set IP address assigned from customer input. See the label
attached to the portal for the IP address in either case (refer back
to Figure 1). An IP address must always be present for Ethernet
IP network communication. Set the IP address DIP switch (switch
3 in Figure 8) on the BACLink portal as either default or assigned.
(Switches 1 and 2 are disabled.)
B. Set BACLink default address.
The default IP address is
192.168.168.xxx. The xxx indicates the final portion of the IP
address which is set using the rotary switches on the BACLink
portal. The final portion of the address identifies the BACLink portal
with a unique address on the BACnet network. For example,
using the default address, Figure 9 shows the BACLink portal
address configured as 192.168.168.3. Set the user-assigned final
portion of the portal network address using the rotary switches.
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
10's digit
1's digit
Figure 8. BACLink DIP Switches
Figure 9. Rotary Address Switches
C. Set BACLink portal address DIP switch.
The BACLink
portal DIP switch 5 (refer back to Figure 8) must correspond to the
final portion of the IP address setting. Set the switch to +0 for
addresses 0 to 99 or to +100 for addresses 100 to199.
3. Set configuration jumpers on portal
See the port connector label attached to the BACLink portal for the
factory-configured port assignments (refer back to Figure 1).
Set port 2 configuration jumpers for communication type.
When using port 2 on the BACLink portal for communication with
the drives, set the port 2 configuration jumpers for EIA-485
(2-wire). Figure 10 illustrates the appropriate setting. EIA-485
(2-wire) is the factory default setting.
When using port 1.
Port 1 must be programmed for operation at
the factory based upon customer ordering data. When using
port 1 on the BACLink portal for communication with the drives, set
the port 1 DIP switch (refer back to Figure 8) for
ARC156
when
using an ARCnet interface to the drives or
Other
for EIA-485 or
additional options.
EIA-485
485-4w
485-2w
EIA-232
1
2
3
4
IP Address
Switch 2
Port 1
Off/ On
Defa ult/ Assig ned
Portal Address
+0/ +100
ARC156/ Other
Off/ On
5
Switch 1
For Ethernet connection without IP, an IP address is not used.
Use the rotary address switches to assign the media access
control (MAC) address.