 PCP communication

Via the CMD tool you are able to read and write to

parameters and read the English parameter text of

each parameter.

To start PCP communication you must be in Monitor

state. Click on the station number and click on the

right mouse button and choose 

Device

Parametization

.

The dialog box will now show 

Danfoss, VLT 5000,

Profile: 21. 

In order to be able to read in all

parameters in the VLT frequency converter select

Device

 and 

Read Parameter List

. The CMD tool will

now start reading all parameters, this will take 3-4

minutes.

When all parameters have been read, CMD will

show the first parameter 55F1 Hex 

Language

 at the

first row.

55F1 Hex corresponds to 22001

D

. This means that

all VLT 5000 parameters simply can be accessed by

adding 22000

D

 to the VLT 5000 parameter. For

example if you want to write to parameter 207

Ramp up time 1 

you must write to 22207

D

 (56BF

Hex).

The CMD tool can only indicate parameters by

hexadecimal numbers.

If you want to change the value of parameter 207

Ramp up time 1

 to 10 sec you must write 1000 in

column next to index 56BF Hex. You have to

enter 1000 because VLT parameter 207 has a

conversion index of -2 = 10

-2

.

Highlight the row by clicking on 60 and click on 

F5

Write Value

. The ramp up time in parameter 207

has now been changed to 10 sec.

At the bottom of the parameter list the Interbus

Drivecom 21 objects are available. These objects

are not accessible via the LCP but only via Interbus

PCP communication.

Please have a look at the Interbus operating

instructions for further description of these objects.

Содержание VLT 5000

Страница 1: ...e Green PCP Communication running NO PCP Communication running UL Power OK Green Voltage within permissible range No Voltage All examples in this instruction are shown with a PLC card as an Interbus m...

Страница 2: ...ad In is finished Please look at the bottom of the screen After the Read In CMD will indicate each VLT frequency converter with a DriveCom symbol a station number and an ID number Next step is to conf...

Страница 3: ...ram profile must be set to Fieldbus option If you change the operating state from Online to Monitor you can write the control word and refe rence to the VLT frequency converter In Monitor state you ca...

Страница 4: ...rol for controlling the VLT frequency converter Please notice that the control word will change when you change the states The control word is now 7F Hex Press Close The Manufactured Specific bits are...

Страница 5: ...st row 55F1 Hex corresponds to 22001D This means that all VLT 5000 parameters simply can be accessed by adding 22000D to the VLT 5000 parameter For example if you want to write to parameter 207 Ramp u...

Страница 6: ...PCD data The data for the VLT frequency converter in our PLC program starts at address 20 So we have to map address 20 to the Interbus card in the VLT frequency converter This is done with the CMD to...

Страница 7: ...ontroller board and select Address Monitor P22 Input 201E Shows the actual reference from the VLT frequency converter P22 Output 2000 Hex Here you can write a reference tothe VLT frequency converter P...

Отзывы: