4

MN.50.U1.02 - VLT is a registered Danfoss trademark

VLT

®

 5000 and Interbus CMD

 Drivecom profile, cont.

By clicking Settings you can setup the Drivecom

monitor.

In 

Manufactured Specific Control bits

 Danfoss have

choosen to implement Jog, Setup select and

Reversering, and in 

Manufactured Specific Status

the Running Status bit is implemented.

Press OK when the Monitor settings are done.

Click on Device Control for controlling the VLT

frequency converter. Please notice that the control

word will change when you change the states.

The control word is now 7F Hex. Press Close.

The 

Manufactured Specific bits

 are now added to

the Drivecom monitor.

Type a reference in rpm below 

Set Speed

 and click

on Write to send the reference to the VLT frequency

converter. The rpm value can now be seen in the

VLT display as a reference from 0 - 100 %.

Click 4 for 

Ready to Switch On

 and click 2 for

Switch On.

By Clicking 5 the VLT frequency converter should

start the motor. Do not forget to set VLT parameter

502 Coasting to 

Bus.

Содержание VLT 5000

Страница 1: ...e Green PCP Communication running NO PCP Communication running UL Power OK Green Voltage within permissible range No Voltage All examples in this instruction are shown with a PLC card as an Interbus m...

Страница 2: ...ad In is finished Please look at the bottom of the screen After the Read In CMD will indicate each VLT frequency converter with a DriveCom symbol a station number and an ID number Next step is to conf...

Страница 3: ...ram profile must be set to Fieldbus option If you change the operating state from Online to Monitor you can write the control word and refe rence to the VLT frequency converter In Monitor state you ca...

Страница 4: ...rol for controlling the VLT frequency converter Please notice that the control word will change when you change the states The control word is now 7F Hex Press Close The Manufactured Specific bits are...

Страница 5: ...st row 55F1 Hex corresponds to 22001D This means that all VLT 5000 parameters simply can be accessed by adding 22000D to the VLT 5000 parameter For example if you want to write to parameter 207 Ramp u...

Страница 6: ...PCD data The data for the VLT frequency converter in our PLC program starts at address 20 So we have to map address 20 to the Interbus card in the VLT frequency converter This is done with the CMD to...

Страница 7: ...ontroller board and select Address Monitor P22 Input 201E Shows the actual reference from the VLT frequency converter P22 Output 2000 Hex Here you can write a reference tothe VLT frequency converter P...

Отзывы: