VLT® 4000 VT
■
Line Supply, 3 x 525 - 600 V
Output
VLT type
4
4100
4125
4150
4200
4250
4300
Output Current
I
VLT,N
[A] (550 V)
104
131
151
201
253
289
I
VLT, MAX
(60 s) [A] (550 V)
114
144
166
221
278
318
I
VLT, N
[A] (575 V)
99
125
144
192
242
289
I
VLT, MAX
(60 s) [A] (575 V)
109
138
158
211
266
318
Output
S
VLT,N
[kVA] (550 V)
99
125
144
191
241
275
S
VLT,N
[kVA] (575 V)
99
124
143
191
241
288
Typical shaft output
P
VLT,N
[kW]
75
90
110
132
160
200
Typical shaft output
P
VLT,N
[HP]
100
125
150
200
250
300
Max. copper cable cross-section
to motor
and loadsharing
4)
[mm
2
/AWG]
2)
120
4/0
120
4/0
120
4/0
2 x120
2 x4/0
2 x120
2 x4/0
2 x120
2 x4/0
Max.
aluminium cable
cross-section power, NEMA
1
4)
[mm
2
/AWG]
2)
185
300mcm
185
300mcm
185
300mcm
2x185
2x300mcm
2x185
2x300mcm
2x185
2x300mcm
Min. cable cross-section to motor
and loadsharing
3)
[mm
2
/AWG]
2)
6
8
6
8
6
8
2 x 6
2 x 8
2 x 6
2 x 8
2 x 6
2 x 8
Input
Rated Input Current
I
VLT,N
[A] (550 V)
101
128
147
196
246
281
I
VLT, N
[A] (600 V)
92
117
134
179
226
270
Max. copper cable cross-section
power, NEMA 1
4)
[mm
2
/AWG]
2)
120
4/0
120
4/0
120
4/0
2 x120
2 x4/0
2 x120
2 x4/0
2 x120
2 x4/0
Max.
aluminium cable
cross-section power, NEMA
1
4)
[mm
2
/AWG]
2)
185
300mcm
185
300mcm
185
300mcm
2x185
2x300mcm
2x185
2x300mcm
2x185
2x300mcm
Max. pre-fuses (mains)
1)
[-]/UL
1)
[A]
125
175
200
250
350
400
Efficiency
0.96-0.97
Weight IP00
[kg]
109
109
109
146
146
146
[lbs]
240
240
240
322
322
322
Weight IP20 / NEMA 1
[kg]
121
121
121
161
161
161
[lbs]
267
267
267
355
355
355
Estimated power loss at max.
load (550 V)
[W]
2605
3285
3785
5035
6340
7570
Enclosure
IP00 and NEMA 1
1. See section
Fuses.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP 20. Always comply with national and
local regulations on min. cable cross-section.
4. Connection stud 1 x M8 / 2 x M8.
MG.40.A4.22 - VLT is a registered Danfoss trademark
25
Installation