602 Alarm store (ALARM MEMORY)
0
1
2
3
4
-
-
7
Fault code
[0]
Time
[1]
Value
[2]
Function:
[Index 000.00 - 007.02]. Storage of data in
connection with tripping.
Description of choice:
The fault code gives the cause of a trip occurrence in
the form of a digit code from 1 to 15:
Fault code
Alarm
1
Alarm
2
Overvoltage
3
Undervoltage
4
Overcurrent
5
Ground fault
6
Overtemperature
7
Inverter overloaded
8
Motor overloaded
9
Current limit
10
Trip locked
11
Control card or option card fault
13
Auto-optimisation fault
14
Fault in direct current supply
15
Thermistor input activated, se parame-
ter 400/terminal 16
Time
indicates the total number of operating hours
after which the trip occurred. Display range 0.0 -
999.9.
Value
indicates e.g. at what voltage or current the trip
occurred. Display range 0.0 - 999.9.
Serial communication - the fault code is returned in
the form of a whole number. Time and value are
registered in the form of floating decimal point values.
8 log values are indicated (0-7).
The lowest log number (0) contains the most recent/
last data value saved, with the highest log number (7)
containing the earliest data value.
An alarm can only be represented once. The fault log
is reset after manual initialisation. Regardless of the
log set being studied at any given time, the display
automatically switches to log no. 0 if another trip
occurs.
603 Nameplate (NAMEPLATE)
Value:
★
0 Type (VLT3xxx)
1 Unit voltage (xxx V)
2 Software type
Process
[1]
HVAC
[2]
Profibus Proc
[3]
Profibus HVAC
[4]
Syncron Opt
[5]
Proc
[6]
Modbus HVAC
[7]
3 Software version (vx.x)
Function:
The key data for the unit can be read from the display
or the bus (RS 485).
Description of choice:
Type
indicates the size of unit and the basic functions
involved.
Unit voltage
indicates the voltage for which the unit
was built or set (par. 650).
Software type
indicates whether the software used is
a standard product or specially developed.
Software version
indicates the version number.
★