Drive type
A
B
C
D
0075 2-0114 2
0072 5-0105 5
0041 6-0052 6
80
(3.15)
80
(3.15)
300
(11.81)
100
(3.94)
0140 2-0205 2
0140 5-0205 5
0062 6-0100 6
80
(3.15)
()
80
(3.15)
300
(11.81)
300
(11.81)
0261 2-0300 2
0261 5-0300 5
0125 6-0208 6
50
(1.97)
80
(3.15)
400
(15.75)
250 / 350
(9.84) / (13.78)
()
To change the fan with the motor cables connected, the necessary clearance on the 2 sides of the drive is 150 mm (5.91 inch).
The minimum clearance to change the fan.
Table 7: Necessary Quantity of Cooling Air
Drive type
The quantity of cooling air [m
3
/h]
The quantity of cooling air [CFM]
0003 2-0012 2
0003 5-0012 5
70
41.2
0017 2-0031 2
0016 5-0031 5
190
112
0048 2-0061 2
0038 5-0061 5
0004 6-0034 6
425
250
0075 2-0114 2
0072 5-0105 5
0041 6-0052 6
425
250
0140 2-0205 2
0140 5-0205 5
0062 6-0100 6
650
383
0261 2-0300 2
0261 5-0300 5
0125 6-0208 6
1000
589
Mounting the Unit
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G
| 35
Danfoss A/S ©
2018.06