Index
Parameter
Min
Max
Unit Default
ID
Description
8 = Keypad
9 = Fieldbus
P2.1.14
Jogging speed refrerence
0.00
P2.1.2
Hz
5.00
124 See
P2.1.15
Preset speed 1
0.00
P2.1.2
Hz
10.00
105 -
P2.1.16
Preset speed 2
0.00
P2.1.2
Hz
15.00
106 -
P2.1.17
Preset speed 3
0.00
P2.1.2
Hz
20.00
126 -
P2.1.18
Preset speed 4
0.00
P2.1.2
Hz
25.00
127 -
P2.1.19
Preset speed 5
0.00
P2.1.2
Hz
30.00
128 -
P2.1.20
Preset speed 6
0.00
P2.1.2
Hz
40.00
129 -
P2.1.21
Preset speed 7
0.00
P2.1.2
Hz
50.00
130 -
1
Parameter value can only be changed after the AC drive has been stopped.
7.4.3 Input Signals
Table 56: Basic Settings (Control Panel: Menu M2 -> G2.2.1)
Index
Parameter
Min Max
Unit Default ID
Description
P2.2.1.1
(1)
Start/Stop logic
0
7
-
0
300
Logic = 0
Ctrl sgn 1 = Start forward
Ctrl sgn 2 = Start reverse
Logic = 1
Ctrl sgn1 = Start/ Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/ Stop
Ctrl sgn 2 = Run enable
Logic = 3
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Stop pulse
Logic = 4
Ctrl sgn 1 = Start
Ctrl sgn 2 = Motor potentiometer UP
Logic = 5
Ctrl sgn 1 = Forward pulse (edge)
Ctrl sgn 2 = Reverse pulse (edge)
Logic = 6
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Reverse pulse
Logic = 7
Ctrl sgn 1 = Start pulse (edge)
AB296635287482en-000301 / DPD00903
92 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide