•
•
•
•
•
•
•
•
•
•
•
•
10.156 (ID 412) Reverse
Location in the menu:
P2.2.7.4
(Multi-purpose Control Application)
P2.2.6.11
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that changes the direction when Start signal 2 is used for other purposes.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Contact open: Direction forward
Contact closed: Direction reverse
This command is active when
Start signal 2
(
ID 404
) is used for other purposes.
10.157 (ID 413) Jogging Speed
Location in the menu:
P2.2.7.16
(Multi-purpose Control Application)
P2.2.6.12
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that selects jogging speed for the frequency reference.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Contact closed: Jogging speed selected for frequency reference
See parameter
ID 124
.
Default programming: A.4.
10.158 (ID 414) Fault Reset
Location in the menu:
P2.2.7.10
(Multi-purpose Control Application)
P2.2.6.13
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that resets all active faults.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
CLOSED = Resets all active faults. Rising edge resets the faults.
10.159 (ID 415) Acc/Dec Prohibit
Location in the menu:
P2.2.7.14
(Multi-purpose Control Application)
P2.2.6.14
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that prevents the acceleration and the deceleration of the drive. No acceleration
or deceleration is possible until the contact is open.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
10.160 (ID 416) DC-Braking
Location in the menu:
P2.2.7.15
(Multi-purpose Control Application)
P2.2.6.15
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that starts DC-braking in the STOP mode.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Contact closed: In STOP mode, the DC-braking operates until the contact is opened.
See
ID 1080
.
10.161 (ID 417) Motor Potentiometer Down
Location in the menu:
P2.2.7.8
(Multi-purpose Control Application)
P2.2.7.16
(Pump and Fan Control Application)
AB296635287482en-000301 / DPD00903
218 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......