Parameter
Parameter Details
Specification
Cable specification
Cable jacket diameter (
⌀
)
4-8 mm
Cable type
Shielded Single Pair - 2-wire
Cable shield termination
Via EMC cable clamp
Maximum wire gauge
2.5 mm
2
Maximum cable length
30 m
Sensor Input Specification
Sensor input class
Class A
Nominal output current
12 mA for an 800
Ω
load
Maximum short-circuit output current
24.5 mA
Open-circuit output voltage
+12 VDC
Maximum pulse frequency
16.7 Hz
Direct contact protection
Double/Reinforced insulation
Yes
Short-circuit protection
Yes
Table 4.9 Auxiliary Interface Specifications
1)
A maximum of 100 inverters can be connected in 1 network. If
GSM modem is used for portal upload, the number of inverters in a
network is limited to 50.
2)
For underground use, outdoor burial type cable is recommended
for both Ethernet and RS-485.
3)
Third input is used for compensation of the irradiation sensor.
4)
The number of inverters to be connected in the RS-485 network
depends on which peripheral device is connected.
CAUTION
To ensure fulfilment of IP enclosure rating, correctly
mounted cable glands are essential for all peripheral
cables.
CAUTION
To ensure EMC compliance, shielded cables must be
applied for sensor inputs and RS-485 communication.
Unshielded cables may be applied for alarm outputs.
Other auxiliary cables must pass through the designated
EMC cable clamps to establish mechanical fixing and in
case of shielded cable termination to the shielding device.
Parameter
Condition
Specification
Potential free
contact
Relay output
x 1
Rating AC
250 V AC, 6.4 A, 1600 W
Rating DC
24 V DC, 6.4 A, 153 W
Maximum wire
gauge
2.5 mm
2
Overvoltage
category
Class III
Modem
GSM
Table 4.10 Auxiliary Input Specifications
Technical Data
28
L00410309-09_02
4
4