Installation Guide
Termix HD MIX Compact 28
DH supply temperature too high.
Wrong setting of thermostat or of
automatic controls, if any.
Adjust automatic controls, – see
instructions for automatic controls.
Defective controller. The controller does
not react as it should according to the
instructions.
Call automatic controls manufacturer or
replace the regulator.
Defective sensor on self-acting thermostat.
Replace thermostat – or sensor only.
DH supply temperature too low.
Wrong setting of automatic controls, if any.
Adjust automatic controls – see instructions
for automatic controls.
Defective controller. The controller does
not react as it should according to the
instructions.
Call in automatic controls manufacturer or
replace controller.
Defective sensor on self-acting thermostat.
Replace thermostat – or sensor only.
Wrong placement/fitting of outdoor
temperature sensor.
Adjust location of outdoor temperature
sensor.
Strainer clogged.
Clean gate/strainer.
Too high DH return temperature.
Too small heating surface/too small
radiators compared to the total heating
requirement of the building.
Increase total heating surface.
Poor utilization of existing heating surface.
Defective sensor on self-acting thermostat.
Make sure the heat is distributed evenly
across the full heating surface – open all
radiators and keep the radiators in the
system from heating up at the bottom. It
is extremely important to keep the supply
temperature to the radiators as low as
possible, while maintaining a reasonable
level of comfort.
The system is single pipe loop.
The system should feature electronic
controls as well as return sensors.
Pump pressure too high.
Adjust pump to a lower level.
Air in system.
Vent the system.
Defective or incorrectly set radiator
valve(s). Single pipe loop systems require
special one-pipe radiator valves.
Check – set/replace.
Dirt in the motorized valve or in the
differential pressure controller.
Check – clean out.
Defective motorized valve, sensor or
automatic controller.
Check – replace.
Electronic controller not adjusted correctly.
Adjust according to instructions.
Noise in system.
Pump pressure too high.
Adjust pump to a lower level.
Heat load too high.
Defective motorized valve, sensor or
electronic controller.
Check – replace.
7.3 Disposal
Disposal
This product should be dismantled and its components
sorted, if possible, in various groups before recycling
or disposal.
Always follow the local disposal regulations.
16
DEN-GT
VI.GP.E1.02 / LUK42860
Danfoss District Energy
Содержание Termix HD MIX Compact 28
Страница 17: ...Installation Guide Termix HD MIX Compact 28 Danfoss District Energy VI GP E1 02 LUK42860 DEN GT 17 ...
Страница 18: ...Installation Guide Termix HD MIX Compact 28 18 DEN GT VI GP E1 02 LUK42860 Danfoss District Energy ...
Страница 20: ...Installation Guide Termix HD MIX Compact 28 Produced by Danfoss A S 09 2013 ...