5.4 Schematic diagram
Schematic diagram type 6-8 (example)
DHW
DH
Supply
DH
Return
DCW
HWC
Your substation might look different than the schematic diagram shown.
Schematic description
B
Heat exchanger, DHW
4
Safety valve
30 Flow control with control valve
D Hot water tank
11 Domestic hot water pump
36 Balancing valve
G Electronic controller, DHW
13 Charging pump
40 Immersion sensor
L
Border of delivery
18 Thermometer
43 Ball valve closed
1
Ball valve
19 Surface sensor
44 Immersion sensor
2
Single check valve
27 Actuator
DHW:
Domestic Hot Water
DCW:
Domestic Cold Water
HWC:
Hot Water Circulation
DH Supply:
District Heating Supply
DH Return:
District Heating Return
5.4.1 Technical parameters
Technical parameters
Nominal pressure:
PN 16
Max. DH supply temperature:
120 °C
Min. DCW static pressure:
0.5 bar
Brazing material (HEX):
Copper
Heat exchangers test pressure:
30 bar
Sound level:
≤ 55 dB
Danfoss District Energy
VI.EH.D4.02 / LUK41570
DEN-GT
11