Description
3.4 Features
16
SONO 3500 CT
Operating Instructions, 07/2019, VI.SH.P2.02
3.4
Features
The following features are available:
●
Mains-powered transmitter
●
Battery backup with 3.6 V Lithium single D-cell battery
●
Suitable for sensor pipe diameters from DN 100 (4") up to DN 1200 (48")
●
IP67 (NEMA 4X/6) rated polyamide transmitter enclosure
●
Factory preset to the nominal dimensions of pipe type and pipe size
●
Programming via SIMATIC PDM
●
Local control panel with single push button, 8-digit display and IrDA optical interface for
communication with SIMATIC PDM
●
Display showing accumulated volume as well as instantaneous flow rate. The displayed
units are m
3
/h and m
3
●
Two digital outputs for volume pulse or alarm
Applications
The main application for the type-approved SONO 3500 CT flowmeters is measurement of
water flow in district heating plants, local networks, boiler stations, substations, chiller plants,
irrigations plants, and other general water applications.
Integration
The flowmeter pulse output is often used as input for an energy meter or as input for digital
systems for remote reading. The transmitter has two pulse outputs, with functions that can
be individually selected, and integrated IRDA (optical eye) communication interface (Modbus
RTU).
The settings of the transmitter, for example flow and pulse output rate, are defined when
ordering the complete flowmeter. If the flowmeter forms part of an energy meter system for
custody transfer, no further approvals are needed, except possible local approvals.
Transmitter communication solutions
The transmitter supports Modbus RTU communication via the optical IrDA interface at the
display, enabling the change of different transmitter settings using the SIMATIC PDM
software tool.
The transmitter is configured in a combination of hardware (HW) and firmware (FW). For the
communication and parametrization via SIMATIC PDM a firmware-specific device
description (EDD) is needed.
Содержание SONO 3500 CT
Страница 1: ...Ultrasonic Flowmeter Operating Instructions SONO 3500 CT 07 2019 Edition ...
Страница 2: ......
Страница 8: ...Table of contents 6 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 14: ...Introduction 1 5 Further Information 12 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 38: ...Electrical connection 5 5 Sealing of SONO 3500 CT 36 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 50: ...Commissioning 6 4 Commissioning via PDM 48 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 54: ...Functions 7 4 Hardware key 52 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...
Страница 64: ...Service and maintenance 8 7 Battery disposal 62 SONO 3500 CT Operating Instructions 07 2019 VI SH P2 02 ...