7369053-0 SIBC
VI.HB.C1.00 © Danfoss 5/02
1
Instructions
VM2, VB2 2-way
065R9074
065R9074
DN
L (mm)
15
65
20
70
25
75
32
100
40
110
50
130
DN
L
1
(mm)
15
131
20
142
25
159
32
196
40
196
50
228
DN
L
2
(mm)
15
139
20
154
25
159
32
184
40
294
50
330
DN
L
3
(mm)
15
69
20
74
25
79
32
104
40
114
50
134
VM2
VB2
Manual override
Instructions
AVQM, AVQMT – PN 16, 25 / DN 15-50
73695050 DH-SMT/SI
VI.DB.T2.1N © Danfoss 09/2009
1
DN 15-32
DN 15-50
DN 32-50
DN 15-50
DN 32-50
DN 15-50
DN 32-50
∆
p = 0.2
∆
p = 0.2
∆
p = 0.2
∆
p = 0.2
∆
p = 0.2
∆
p = 0.2
∆
p = 0.2
AVQM (PN 16)
AVQM (PN 25)
AVQMT (PN 25)
AVQMT/AVT (PN 25)
ENglIsh
Flow (and temperature) controller with integrated control
valve AVQM, AVQMT
www.danfoss.com
Page 7
DANsK
Flow- (og temperatur-)regulator med indbygget motorventil
AVQM, AVQMT
www.danfoss.dk
Side 9
DEUTsCh
Volumenstrom (und Temperatur-) Regler mit Motorstellventil
AVQM, AVQMT
www.danfoss.de
Seite 11
EsPAÑOl
Regulador de caudal (y temperatura) con válvula de control
integrada AVQM, AVQMT
www.danfoss.es
Página 13
slOVENŠČINA
Regulator pretoka (in temperature) z regulacijskim ventilom
AVQM, AVQMT
www.danfoss.si
Stran 15
POlsKI
Regulator przepływu (i temperatury) z zaworem
regulacyjnym AVQM, AVQMT
www.danfoss.pl
Strona 17
MAgyAr
Térfogatáram(és hőmérséklet) szabályozó, motoros
szabályozó-szeleppel egybeépítve AVQM, AVQMT
www.danfoss.hu
Oldal 19
srPsKI
Uputstvo AVQM, AVQMT-PN 16, 25/DN 15-50
grejanje.danfoss.com
Strana 21
Alternative actuator
AMV150 and valve
housing VS2
99
Instructions for installation and use
S 22
Danfoss District Energy
VI.IE.D1.02
DKDHR
General information
PLEASE NOTE! Some models may have a slightly different appearance,
but the control function is in principle the same as described below.
Commissioning
Commission the unit in accordance with instructions on page 6 -7.
Filling the system
Filling of water to the heating system must be done according to the
instructions on page 6 (item 5 - GETTING STARTED).
Check and tighten all connections before adding water to the system,
as vibrations during transport may have caused leaks. After having
added water to the system, tighten all the connections before per-
forming leak test.
Then heat up the system, check the connections and tighten once
again if necessary.
Before adding water to the system and first start-up, check if:
- pipes are connected according to the circuit diagram,
- heat meter is mounted,
- shut-off valves are closed,
- threaded and flanged connections are tightened.
Differential pressure controller (common return pipe
- only Application A266)
The differential pressure controller, Danfoss AVP-F reduces the high
fluctuations in pressure in the district heating network, ensuring a
small and constant operating pressure across the unit. This ensures
optimum operating conditions for the control equipment.
The differential pressure controller closes on rising differential
pressure. The differential pressure controller is preset to a fixed value
from factory and should not be adjusted afterwards.
Please refer to enclosed producer instructions for further information.
Instructions AVP-F
Danfoss ECL Comfort 310
The substation is supplied with an Danfoss ECL 310 controller. The ECL
controller is supplied with an ECL Application Key A266. The application
Key contains information about application, language and factory set-
tings, adapted to the type of system, for which it is ordered.
Note! Various applications can be loaded.
The controller is factory-set for local language and the running time for
the actuator (heating circuit) is preset for the actual application.
General controller settings such as “Time and Date” must be entered
during commissioning of the controller. And also the desired supply
flow temperature must be set.
Please refer to enclosed manufacturer instructions for the ECL 210/310
controller to
set the required temperature for the heating circuit
:
ECL Application Key Box with ECL Comfort 210/310 user guide and
mounting guide, for further information.
We recommend that your order commissioning of the controller with your
local Danfoss representative.
Note, in systems that feature only floor heating it is important that the
supply temperature does not exceed 35°C, and ALWAYS check the in-
structions from the floor supplier ( typically for wooden floors).
Ac valve, unit with control of heating- and DHW circuits,
Application A266
For controlling the heating circuit the S 22, A266 is supplied with a
Danfoss AMV 10 actuator with Danfoss valve type VM2, placed on the
primary return flow pipe. The AMV actuator is electrically wired to the
controller from factory.
Please refer to enclosed producer instructions for further information.
Instructions AMV10
Factory setting
The actuator has undergone a functional test and is preset from factory.
In the event of operating disturbances the actuator can be shut off man-
ually in accordance with enclosed instructions, by turning the manual
override knob on top of the actuator clockwise. Please note that the
knob can be “tight” to turn.
8.
Adjustment and commissioning, heating circuit