INSTALLATION 

Attention:   

A standard electrical box is required: Wiring work should be done according to wiring diagram. 

Water, mud etc. impurity should be kept outside of thermostat or damage will occur   

                             

 

 

1. Open the clip 

 

 

2. Wiring 

 

3. Fix thermostat with two bolts 

 

 

4. Lock surface and finished 

Содержание RESD Series

Страница 1: ...tatus Cool Heat Ventilation Fan Speeds Low Medium High and Auto Room temperature display Temperature setting display FCU valve Clock week display SPECIFICATIONS Sensing element NTC Accuracy Temperature 1 C Time 1 min month Set point range 5 to 35 C Display range 0 to 55 C Operation environment T min 0 C T max 45 C Power supply 85 to 260V 50 60Hz Switch current rating Resistive 2 A Inductive 1 A Sw...

Страница 2: ...en room temperature and setting temperature exceed 1 C Auto MED speed When exceed CAuto HI speed When e xceed 3 C CLOCK CALIBRATION Clock setting Press till to display hh mm and hh flash press or to adjust hour press mm flash press or to adjust minute Press week flash press or to adjust Mon to Sun TIMER ON AND TIMER OFF Timer on Press till to display and ON and all flash and also hh flash press or...

Страница 3: ...n the LCD and keypads are locked for fear anyone operated To disable the function Press button for 5 seconds till disappeared on the LCD the function will be disable AUTO RESTART Option When the thermostat is at ON status for 6 seconds if power cut it will return back to running automatically with the status how it is one minute ago after power coming back When the thermostat is at OFF status for ...

Страница 4: ...electrical box is required Wiring work should be done according to wiring diagram Water mud etc impurity should be kept outside of thermostat or damage will occur 1 Open the clip 2 Wiring 3 Fix thermostat with two bolts 4 Lock surface and finished ...