Installation

Instructions

RA2000 One Pipe Steam (1PS)

Thermostatic Radiator Valve

VISXA222 © Danfoss 04/16

Description: 

RA 2000 one pipe steam (1PS) thermostatic radiator valve is 

a three part assembly consisting of a valve body (013G0140), 

air vent (013L8011) and thermostatic operator (air vent and 

thermostatic operators are sold separately). See Thermostatic 

Operator Selection instructions below to determine correct 

operator for your application.

   

The 1PS thermostatic radiator valve assembly is designed to 

provide accurate temperature control and quiet operation on 

all “non-vacuum” low pressure (max. 15 psig) one pipe steam 

heating systems.

Note:

 For proper valve operation, the steam supply must be 

cycled by a boiler control. Do not install the 1PS thermostatic 

radiator valve assembly in a zone where the boiler is cycled by 

an existing space thermostat. 1PS thermostatic radiator valve 

assembly is not recommended for copper fin tube radiators.

 

Function:

A temperature change around the thermostatic operator’s 

sensor results in a modulating action of air venting from the 

radiator or convector.

When the thermostatic operator calls for heat, steam enters 

the radiator and pushes air out through the vent. When the 

setting temperature is reached, the 1PS valve will be closed 

and no further air venting takes place. 

The venting action occurs during each system (boiler) on-cycle 

only when heat is required. Air will re-enter the radiator during 

RA 2000 1PS Thermostatic 

Radiator Valve 

(Complete Assembly)

Thermostatic 

Operator

(013G8250 shown)

Air Vent  

(013L8011)

1PS Valve

  

(013G0140)

1/8” 45

°

 

Street Elbows 

(Optional)

(013L8300)

Spare Parts:

Packing Gland

(013G0290)

Vacuum Breaker

(013U7175)

Free Standing Radiators/Built-In Sensor:

 

Use built-in 

sensor when room air can pass freely over the sensor.

Free Standing Radiators/Remote Sensor:

 

Use remote 

sensor when room air cannot pass freely over the sensor.

a)

  

 

  

(013G8250)             (013G8240)

Use standard or 

tamper resistant model

with combined dial/operator/sensor.  

Always install the operator horizontally.

b)

 

 

  

 (013G8252)

Use dial / operator with remote sensor.  

The sensor and capillary tube may be 

extended  up to 6’ and can be easily 

wall mounted.

Convectors:

 The one-pipe low-pressure steam convector is 

inaccessible; room air cannot continually pass freely over the 

valve.

Enclosed Radiators:

 

The cabinet enclosed radiator 

configuration  requires  that  the  dial  and  sensor  be  mounted 

separately, away from the valve.

Available for mounting the 1PS 

assembly onto convectors are 1/8” 45

°

 

street elbows, part number 013L8300.  

When ordering these elbows two  

pieces are needed per convector.

    

(013G8564)

    

Use operator with separate remote 

dial and remote sensor.  Place the 

remote sensor beneath the element or 

on a draft-free wall.  The remote dial 

mounts on the enclosure or wall.

(013G8562)

Use dial / operator with remote sensor.  

The sensor and capillary tube may be 

extended  up to 6’ and can be easily 

wall mounted.

the system off-cycle via a patented “‘across the seat” vacuum breaker. This 

eliminates condensate build-up and allows natural system aspiration to occur.

Thermostatic Operator Selection:

Tamper 

Resistant

Standard

Содержание RA2000

Страница 1: ...mostatic Radiator Valve Complete Assembly Thermostatic Operator 013G8250 shown Air Vent 013L8011 1PS Valve 013G0140 1 8 45 Street Elbows Optional 013L8300 Spare Parts Packing Gland 013G0290 Vacuum Breaker 013U7175 Free Standing Radiators Built In Sensor Use built in sensor when room air can pass freely over the sensor Free Standing Radiators Remote Sensor Use remote sensor when room air cannot pas...

Страница 2: ... the valve or vent Boiler Steam supply must be cycled by a reset control and must not run at constant pressure which would prevent air from entering back into the system Make sure that free standing radiators or cast iron convectors are properly pitched and that hand valves are FULLY open To aid in preventing overheating of rooms that are temperature satisfied boiler steam pressure must be kept lo...

Страница 3: ... such that the orientation of the air vent port is up The piping of an extension between the radiator and valve body should not be done 3 Tighten the air vent 013L8011 to the valve body If using an air vent not supplied by Danfoss it must be a straight shank vent 4 Mount the thermostatic operator to the valve Refer to the installation instructions included with the thermostatic operator for proper...

Страница 4: ...ation Move remote sensor or dial sensor to a different location The vacuum breaker mechanism may be clogged with debris Verify if excessive pressure is within system Under heating within room Ensure thermostatic operator is in an appropriate location Move remote sensor or dial sensor to a different location The air vent may be stuck closed Check riser air vent for main system Check the pitch of th...

Отзывы: